Battery screen, Metering – Outback Power Systems GS4048A Operators Manual User Manual

Page 50

Advertising
background image

Metering

48

900-0161-01-00 Rev A

Charge

displays the kilowatts and AC amperage consumed for the inverter to charge the battery bank. This

line also shows the present charging stage.

Load

displays kilowatts and AC amperage consumed by devices on the inverter’s output. It can be the same

as

Invert

.

Buy

displays the kilowatts and AC amperage brought into the inverter’s input for both charging and loads.

This is usually a total of

Charge

and

Load

.

Battery

displays the uncompensated battery voltage.

AC Out

displays the AC voltage measured at the inverter’s output (the sum of the L1 and L2 readings). If an

AC source is present, this reading is usually the same as

AC In

.

AC In

displays the AC voltage measured at the inverter’s input from an AC source (the sum of the L1 and L2

readings). This number may be erratic or inaccurate upon first connection until the inverter synchronizes
with the input source.

AUX

displays the current status of the inverter’s Auxiliary (AUX) 12-volt output.

Relay

displays the current

status of the inverter’s Auxiliary relay contacts. (See page 41.)

A diode symbol may appear to the left of the screen name to indicate “diode charging” mode. This is a
mode that allows fine control of charging, selling, and load support. It does not visibly affect operation.

From either

L1 Phase or L2 Phase, the <Graph> soft key brings up a series of screens which plot

various types of data over time on the MATE3 screen.

Battery Screen

From the

L2 Phase screen, the <Next> soft key brings up a screen showing charger status, charger

settings, and battery voltage and temperature information.

Figure 14

Battery Screen

Screen items:

Actual

displays the uncompensated battery voltage.

Absorb

displays the charger’s Absorption voltage setting. (See page 29.)

Float

displays the charger’s Float voltage setting. (See page 30.)

Equalize

displays the charger’s Equalization voltage setting. (See page 33.)

Temp Comp

displays the corrected battery voltage using temperature readings from the Remote

Temperature Sensor (RTS). If no RTS is present,

Temp Comp

and

Actual

will read the same. (See page 33.)

Batt Temp

displays the battery temperature in degrees Celsius, as measured by the RTS. It is only valid for

port 1 on the HUB. If other ports are selected, or if no RTS is present, the characters ### will be displayed.

Re-Float

displays the Re-Float setting which was programmed into the inverter’s charger. This is the

voltage used for the inverter to return from Silent mode to the float stage. (See page 30.)

Sell RE

voltage is the target voltage used by the inverter for both the Offset and grid-interactive functions

when the charger is otherwise inactive. (See pages 15 and 35.)

The

<Warn> and <Error> keys bring up screens with various fault information. See the next section.

NOTE: The charger settings cannot be adjusted on this screen.


An arrow will appear to the right of

Absorb, Float, or Equalize to

indicate that the charger is in that stage. The arrow will not appear if

the charger is in the Bulk stage, or if it is inactive.