Installation 4-4

4 . 2 . 1

Transformer Wiring

One of two types of transformers is installed in the starter assembly. Check
the wiring configuration of the transformer before applying ac power to
the HPU.

Standard
transformer wiring

Figure 4-4 shows the jumper wiring required on a standard transformer for source voltages of 460.

H1

X2

H2

X1

H3

460 Vac

H4

VW-C036

Figure 4-4. Standard Transformer Wiring Configuration

Optional
transformer wiring

An optional multi-tap transformer may be used for source voltages other
than 230 Vac and 460 Vac. The following figure shows the typical wiring
required for various voltages. Source voltages are applied to terminals H1
through H5 as shown. An output voltage is tapped from terminals X1
through X4. Check the output voltage with a voltmeter. It should be 110
Vac for systems using 50 Hz power and 115 to 120 Vac for systems with
60 Hz.

X4

VW-C037

X3

X2

X1

H4

H5

H3

H2

H1

208/220/230/240 Vac

380/400/416 Vac

440/460/480 Vac

500/550/575/600 Vac

110/120/125/130 Vac

100/110/115/120 Vac

85/91/99 Vac

jumper

Figure 4-5. Typical Multi-Tap Transformer Wiring Configuration