Setting up run on demand (rod) – MTS Series 505G2 SilentFlo Hydraulic Power Unit Model 505G2-180 User Manual

Page 58

Advertising
background image

Descriptions

Control

Flow Meter Not Present- gray: In this state, there is no flow
meter and the ROD option can not be used. However, the
Auto feature can be used; see “Auto”.

Flow Meter Present - black: In this state, the flow meter is
present and the ROD option (if purchased) can be used.

Pushbutton/Indicator. Pushbutton used to define which units
are displayed for hydraulic fluid flow. Pressing the button
alternates between the states.

Flow Display In GPM/Flow Display in
LPM

Flow Display in GPM - gray.

Flow Display in LPM - gray.

Setting Up Run On Demand (ROD)

The ROD option automatically starts or stops pumps to meet the hydraulic flow demand from the system.
The PLC monitors the hydraulic fluid flow. When the flow changes beyond a trigger point for a set period of
time, one of the pumps is turned on or off.

Refer to the Auto Run table for a description of the controls referenced in the following procedure.

1. From the current screen, press the AUTO Setup button on the Main screen. When the Auto Setup screen

displays, make sure the Flow Meter indicator is in the Flow Meter Present state (blue-green).

2. Set the ROD Flow Buffer.

If necessary, press the associated value pushbutton to display the numeric keypad and change the value.
Press Enter to set the value and return to the Auto Setup screen. The range shown on the numeric keypad
depends on the number of pump modules installed.

3. Check the ROD On Delay.

If necessary, press the associated value pushbutton to change the delay time. Use the popup panel
described above to increase or decrease the delay.

4. Check the ROD Off Delay.

If necessary, press the associated value pushbutton to change the delay time. Use the popup panel
described above to increase or decrease the delay.

5. Check the Rated Flow Per Module.

This value should only require change if the HPU is provided with pump modules that have a different full
flow rating.

6. Press the Main Display button to return to the Main Display screen.

7. Press the ROD button to enable the run on demand option. The button will turn green.

8. Press the Pump #_ Enabled button for those pumps you want active for run on demand.

58 Series 505G2 SilentFlo™ Hydraulic Power Unit Product Information