Troubleshooting 5-9

b. On the top of the linking device, move the jumper to the left-most

contact position then back to the right-most contact position.

c. Close RSFieldBus.
d. On the PC Host in the c:\Program Flies\Rockwell

Software\RSFieldbus\OLEServers\ directory delete the
IDShellHSE.bin file.

e. Restart RSFieldBus.
f. Load your project.
g. Apply power to the linking device. Allow the linking device to

completely start up as indicated by the H1 channel activity LEDs
blinking.

h. Go online in RSFieldBus and monitor the H1 LiveList.
i. The linking device should now be visible.

Does the Linking Device Appear in the H1 Live List Now?

Yes: Done

Are There any Other H1 Devices on the Network?

No:

a. Contact Tech Support.

Or:

a. Disconnect any other H1 devices from the network.

Does the Linking Device appear in the H1 Live List Now?

No:

a. Contact Tech Support.

Or:

a. Manually resolve address or BOF class conflicts between the other

devices and the linking device.

b. Re-connect the devices to the network.

Does the Linking Device Now appear in the H1 Live List Now?

Yes: Done.

No:

a. Call Tech Support.