Rockwell Automation 7000A PowerFlex Medium Voltage AC Drive (A Frame) - ForGe Control (PanelView 550) User Manual
Page 25
 
 
 
Drive Installation
2-3
7000 “A” Frame
7000A-UM151D-EN-P – March 2013
(H) The equipment must be kept clean. Dust in the equipment
decreases system reliability and inhibits cooling.
(I)
Power cable lengths to the motor are virtually unlimited due to
the near sinusoidal voltage and current waveforms. Unlike 
voltage source drives, there are no capacitive coupling, dv/dt, 
or peak voltage issues that can damage the motor insulation 
system. The topology utilized in the PowerFlex 7000 medium 
voltage AC drive does not produce dv/dt or peak voltage 
problems, and has been tested with motors located up to 15 
kilometers from the drive. 
(J)
Only personnel familiar with the function of the drive should
have access to the equipment.
(K) The drive is designed for front access and should be installed
with adequate and safe clearance to allow for total door 
opening. The back of the unit may be placed against a wall 
although some customers prefer back access also. 
A T T E N T I O N
A T T E N T I O N
An incorrectly applied or installed drive can 
result in component damage or a reduction in 
product life. Ambient conditions not within 
the specified ranges may result in 
malfunction of the drive. 
Generator Note:
A T T E N T I O N
A T T E N T I O N
Verify that the load is not turning due to the 
process. A freewheeling motor can generate 
voltage that will be back-fed to the equipment 
being worked on.