Publication 1794-UM064B-EN-P - May 2014

14 Communicate With Your Module

1794-OB8 – 8 Point Discrete Output Module Image Table Mapping

1794-OB16 – 16-point Discrete Output Module Image Table Mapping

1794-IB16 Input Delay Times

Description

Selected
Filter Time

02

01

00

Filter Time for Inputs 00…11

05

04

03

Filter Time for Inputs 12…15

0

0

0

Filter Time 0 (default)

0.256 ms

0

0

1

Filter Time 1

0.512 ms

0

1

0

Filter Time 2

1 ms

0

1

1

Filter Time 3

2 ms

1

0

0

Filter Time 4

4 ms

1

0

1

Filter Time 5

8 ms

1

1

0

Filter Time 6

16 ms

1

1

1

Filter Time 7

32 ms

1794-OB8 Memory Map

Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Size

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Words

Not used

Read Word 0

Not used

O7

O6

O5

O4

O3

O2

O1

O0

Write Word 0

Not used

Write Word 1

Where:

O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, and so on)

1128