14 Communicate With Your Module
1794-OB8 – 8 Point Discrete Output Module Image Table Mapping
1794-OB16 – 16-point Discrete Output Module Image Table Mapping
1794-IB16 Input Delay Times
Description
Selected
Filter Time
02
01
00
Filter Time for Inputs 00…11
05
04
03
Filter Time for Inputs 12…15
0
0
0
Filter Time 0 (default)
0.256 ms
0
0
1
Filter Time 1
0.512 ms
0
1
0
Filter Time 2
1 ms
0
1
1
Filter Time 3
2 ms
1
0
0
Filter Time 4
4 ms
1
0
1
Filter Time 5
8 ms
1
1
0
Filter Time 6
16 ms
1
1
1
Filter Time 7
32 ms
1794-OB8 Memory Map
Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Words
Not used
Read Word 0
Not used
O7
O6
O5
O4
O3
O2
O1
O0
Write Word 0
Not used
Write Word 1
Where: