5-2 Calibrating Your Module
Tools and Equipment
To calibrate your analog I/O modules, you will need the following
tools and equipment:
Calibration Method
Calibration is done through the I/O Configuration Software which is
part of your programming software package, such as RSLogix 5.
Select the Calibration tab in the software and follow the instructions
for complete module calibration..
Tool or Equipment:
Description:
Precision Resistors
High precision resistors:
383W, 0.01%, 5ppm/
o
C
100W, 0.01%, 5ppm/
o
C
10kW, 0.5%, 5ppm/
o
C
Precision Voltage Source
+320mV, 1mV resolution
PC and Interconnect Cable
Programming terminal for A-B family processors