HSL Function Library

103

@ Argument

card_ID: Specifies the HSL master card index. Typically, the sys-

tem assigns the board index sequence. The index starts from 0.

connect_index: For PCI-7851, the valid value is 0. For PCI-

7852 and PMC-7852/G, the valid value is 0 or 1.

slave_No: Specifies the slave module with slave index that wants

to perform this function. The valid value is 1 to 63.

signal_range: The single range of analog input setting.

For HSL-AI16AO2-M-VV

0: ± 1.25 V
1: ± 2.5 V
2: ± 5 V
3: ± 10 V

For HSL-AI16AO2-M-AV

0: ± 5 mA
1: ± 10 mA
2: ± 20 mA
3: ± 20 mA

*signal_range: Reads back the single range of analog input

setting.

For HSL-AI16AO2-M-VV

0: ± 1.25 V
1: ± 2.5 V
2: ± 5 V
3: ± 10 V

For HSL-AI16AO2-M-AV

0: ± 5 mA
1: ± 10 mA
2: ± 20 mA
3: ± 20 mA

*mode: 0: differential type; 1: single-ended input.