Section 2 – wiring, Use separate conduits for high and low voltage, We suggest that minimum ¾-inch conduit be used – DoorKing 9310 User Manual

Page 25

Advertising
background image

SECTION 2 – WIRING

Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the
electrical panel is in the OFF position. A separate power disconnect must be installed at the
operator location.
Permanent wiring must be installed to the operator as required by local electrical
codes. It is recommended that such work be performed by a licensed electrical contractor.

Since building codes vary from city to city, we highly recommend that you check with your
local building department prior to installing any permanent wiring to be sure that all wiring to
the operator (both high and low voltage) complies with local code requirements
.

THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!

1

2

3

4

4

5

5

Not shown in drawing:
1. Secondary entrapment prevention device(s).

1

High Voltage Supply

2

3

4

Lead-in wire(s) from loop(s).

5

Low Voltage Control Wiring

Primary / Secondary interface cable (not supplied).

A separate power disconnect MUST be installed at the operator location

DOORKING, INC., INGLEWOOD, CA 90301

Title:

Date:

Rev.

Dwg. No.

Conduit Requirements

C

5/07

M9310-065-1

The conduit requirements shown are for a typical slide gate operator installation (the
secondary operator is shown for those applications where a secondary operator may be
used). The conduit requirements for your application may vary from this depending on your
specific needs.

Use only sweeps for conduit bends. Do not use 90° connectors as this will make wire pulls
very difficult and can cause damage to wire insulation.

Use separate conduits for high and low voltage.

We suggest that minimum ¾-inch conduit be used.

Be sure that all conduits are installed in accordance with local codes.

9310-065-H-8-08

Page

25

Advertising