2.6 Terminal Identification and Description

2.6.1 Main Terminal (P1)

1.

24 VOLT COMMON
Same as terminal 13.

2.

OPEN / RADIO RELAY
Functions same as terminal 4.

3.

24 VOLT RADIO POWER

4.

FULL OPEN / CLOSE INPUT
When gate is closed, input will open gate to full position.
When gate is open and auto close timer is turned on, input will re-set and hold timer.
When gate is open and auto close timer is turned off, input will close gate.
When gate is closing, input will reverse gate.

5.

PARTIAL OPEN INPUT

Gate will open to PARTIAL limit setting. Functions same as terminal 4.

6.

STANDARD REVERSE / STOP INPUT
When gate is fully closed or in the opening cycle, this input has no affect on the gate
operator.
When gate is open and auto close timer is turned ON, input will re-set and hold timer.
When gate is open and auto close timer is turned OFF, input will prevent gate from
closing.
When gate is closing, input will REVERSE gate if SW 1, switch 7 is OFF.
When gate is closing, input will STOP gate if SW 1, switch 7 is ON.

7.

OPEN INPUT - Use with DoorKing 3 button control station only (P/N 1200-006).

8.

CLOSE INPUT - Use with DoorKing 3 button control station only (P/N 1200-006).

9.

GATE TRACKER - DATA

10.

GATE TRACKER - BUSY

11.

DRY RELAY CONTACT

Operation of relay is dependent on setting of SW 1, switches 4 and 5. Relay contacts
can be set for Normally Open (NO) or Normally Closed (NC) operation. Contact
rating is 1 amp maximum at 24 Volts.

12.

DRY RELAY CONTACT

13.

24 VOLT COMMON
Same as terminal 1.

14. ALARM

OUTPUT

15. ALARM

RESET

16. SOLENOID

LOCK

17. MOTOR

18. MOTOR

19.

115 VAC HOT

20.

115 VAC NEUTRAL

WARNING

HIGH VOLTAGE!