11 main terminal description, 10 wiring for multiple units – intercom mode – DoorKing 1812 Plus User Manual

Page 19

Advertising
background image

1.10 Wiring for Multiple Units – Intercom Mode

DOORKING, INC., INGLEWOOD, CA 90301

Date:

Dwg. No.

Rev.

Title:

2/09

A

M1812P-004

1812 Plus – multiple systems.
Basic wire connections intercom mode.

3

2

A

A

Connect the PHONE OUT terminals directly to home
telephone or an un-used C.O. port on a PBX or KSU
system.

Connect the PHONE IN terminals to the next 1812 PHONE
OUT terminals.

Be sure that the 1812 is programmed in the telephone
mode, unless it is the last 1812 in the system. Refer to B
below.

1

5

5

Mag Lock

Power

Mag Lock

Power

16.5 VAC

20 VA

16.5 VAC

20 VA

B

1

1

4

4

3

2

4

4

B

Up to five (5) 1812 units may be wired in series using this
method: PHONE OUT to PHONE IN; PHONE OUT to
PHONE IN, etc.

Each 1812 must have a unique ATTENTION NUMBER and
each must have a unique MASTER CODE.

The 1812 that is the furthest away from the phone or PBX /
KSU system must be programmed for INTERCOM MODE.
All other 1812 units in series are then programmed for
TELEPHONE MODE.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

Mic
Vol

Master

Code

1 2 3 4 5 6 7 8 9 1011

Speaker

Vol

Keypad

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

Mic
Vol

Master

Code

1 2 3 4 5 6 7 8 9 1011

Speaker

Vol

Keypad

Telephone

Mode

Telephone

Mode

Intercom

Mode

2

Magnetic locks or electric strikes must be powered from a separate UL Listed power
transformer. Do not power strikes or magnetic locks from the 1812 power transformer.

3

1

4

5

Use minimum 18 AWG wire for runs up to 100 feet; 16 AWG wire for runs up to 200 feet. It
is recommended to keep power wire runs as short as possible. Check the power wire chart
for wire size / distance.

Be sure to properly ground all devices. Minimum 12 AWG wire.

Use supplied 16.5 VAC, 20 VA power transformer or UL Listed equivalent. DO NOT
Power this device with a 24 Volt transformer or source voltage.

This device is powered by a 16.5 VAC
transformer. DO NOT power this device with a
24 VAC transformer or power source.

Phone

Jack

Use only twisted pair telephone wire that is rated for direct underground burial. DO NOT
use wire that is intended for indoor applications . Recommend Cat5e Gel Filled
(flooded) UV Resistant Direct Burial Cable. DO NOT run telephone wires and high
voltage wires in the same conduit.
Check the phone wire chart for wire size / distance.

Vehicular Gate

Operator

Pedestrian

Gate / Door

2

nd

1812

1st 1812

Vehicular Gate

Operator

Pedestrian

Gate / Door

1812-161-E-1-10

Page

19