Troubleshooting – Design Dynamics HCA-24-RFN User Manual

Page 13

Advertising
background image

www.desatech.com

115481-01B

13

TROUBLESHOOTING

Note:

In normal operation, LED blinks once

every two seconds; also, LED will be on for one

second after every valid command received by the

receiver/valve' these are not error codes.
Failure codes can occur anytime after the pilot

burner is lit. Failure code timing is 1/4 second

on, 1/2 second off.
Sequence is failure code followed by LED not

blinking for four seconds.
In the event of multiple failure codes, the next

failure code follows the previous failure code by

approximately 3 seconds.

LED Failure Code
(No. of Blinks)

Service Action

8

Replace valve.

7

Confirm stepper motor

connection exists.

5

Confirm fan connection

exists and works.

3

Replace thermopiles.

2

Device too hot. Turn on fan

or if applicable, open glass

doors.

1 short blink

Normal operation

LED Failure Codes and Service Action

WARNING: Turn off and unplug heater and let cool before servicing.

Only a qualified service person should service and repair heater.

IMPORTANT: Valve system troubleshooting should only be accom-

plished by a qualified service technician.

Note:

Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas

supply inlet) is in the "ON" position.

POSSIBLE CAUSE

REMEDY

OBSERVED PROBLEM

1. Defective ignitor (no spark

at electrode)

2. Defective or misaligned

electrode at pilot (spark at

electrode)

3. Gas supply pressure errant

4. Pilot orifice plugged

1. Defective pilot generator

(thermocouple)

Spark ignitor will not light pilot

after repeated triggering of ig-

nitor button

Pilot will not stay lit after care-

fully following the lighting

instructions

1. Check for spark at electrode

and pilot; if no spark and

electrode wire is properly

connected, replace ignitor

2. Using a match, light pilot. If

pilot lights, turn off pilot and

trigger the ignitor button again.

If pilot lights, an improper gas

mixture caused the bad lighting

and a longer purge period is

recommended. If pilot will not

light, check gap at electrode

and pilot - gap should be 1/8"

to have a strong spark. If gap

measures 1/8", replace pilot

3. Check inlet gas pressure. It

should be within the limits as

marked on the rating plate

4. Clean or replace pilot orifice

1. Check pilot flame, it must

impinge on thermocouple

(see Figure 13, page 11).

Clean and/or adjust pilot for

maximum flame impingement

on thermocouple. Ensure that

the connection between the

valve and thermocouple are

tight and secure.