R7184A,B,P,U INTERRUPTED ELECTRONIC OIL PRIMARY

69-1233—2

4

Fig. 5. Typical wiring diagram for line voltage

Aquastat® thermostat and R7184 for an oil burner

system.

Fig. 6. Typical wiring diagram for 24 Vac thermostat

and R7184 for valve-on delay/burner motor off oil

burner system.

Fig. 7. Typical wiring diagram for line voltage

Aquastat® thermostat and R7184B,P,U for valve-on

delay/burner motor-off delay oil burner system.

Simulate ignition failure:

1.

Follow starting procedure to turn on burner, but do
not open oil supply hand valve.

2.

Observe that safety switch locks out approximately
within safety switch timing as indicated on the
label. Indicator light flashes at 1 Hz rate. Ignition
and motor stop and oil valve closes.

OPERATION

The R7184 is a microprocessor-based control. The
indicator light provides diagnostic information for lockout,
recycling and patented cad cell status. There is a manual
reset button to exit the lockout mode and enter the idle
mode. Operation is shown in Table 4.

TROUBLESHOOTING AND
MAINTENANCE

IMPORTANT:

Due to the potential hazard of line voltage, only
a trained, experienced service technician
should perform the troubleshooting procedure.

This control contains no field-serviceable parts.
Do not attempt to take it apart. Replace entire
control if operation is not as described.

To completely troubleshoot an oil burner installation,
check the burner and oil primary control for proper
operation and condition.

The indicator light on the oil primary control provides
lockout, recycle and cad cell indications as follows:

L2

1

R7184

IGNITOR

M17184B

L1

HOT

1

CAD
CELL

2

2

BURNER
MOTOR

L2

BURNER
MOTOR

INTERMITTENT

IGNITOR

INTERRUPTED

CAD
CELL

L1

JUNCTION
BOX

ALARM

T

T

LEGEND:

TO
REMOTE
ALARM
CIRCUIT

SCREW TERMINAL

1/4 IN. QUICK CONNECT TERMINAL

LIMIT

JUMPER

LINE VOLTAGE
THERMOSTAT
OR AQUASTAT®
CONTROL

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

OPTIONAL FEATURE ON SELECT MODELS.

VALVE MAY BE ADDED AS SHOWN.

3

3

VALVE

L2

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

OPTIONAL FEATURE ON SELECT MODELS.

1

R7184

M17185A

L1

HOT

1

CAD
CELL

2

2

OIL
VALVE

BURNER
MOTOR

IGNITOR

L2

BURNER
MOTOR

INTERMITTENT

IGNITOR

VALVE

INTERRUPTED

CAD
CELL

LIMIT

L1

JUNCTION
BOX

ALARM

T

T

LEGEND:

TO
REMOTE
ALARM
CIRCUIT

SCREW TERMINAL

1/4 IN. QUICK CONNECT TERMINAL

LIMIT

T8600

RC

G

Y

R

W

L1
(HOT)

L2

1

FAN RELAY

COOLING
CONTROL

L2

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

OPTIONAL FEATURE ON SELECT MODELS.

1

R7184

M17186A

CAD
CELL

2

2

OIL
VALVE

BURNER
MOTOR

IGNITOR

L2

BURNER
MOTOR

INTERMITTENT

IGNITOR

VALVE

INTERRUPTED

CAD
CELL

LIMIT

L1

JUNCTION BOX

ALARM

T

T

LEGEND:

TO
REMOTE
ALARM
CIRCUIT

SCREW TERMINAL

1/4 IN. QUICK CONNECT TERMINAL

L1

HOT

1

JUMPER

LINE VOLTAGE
THERMOSTAT
OR AQUASTAT®
CONTROL

LIMIT