Fault Finding continued

PROBLEM

CAUSE

SYMPTOM

REMEDY

Fan motor stop working

Every LED at electronics
control board doesn’t light so
its similar to no electric in
circuit

Repair or change the fan

The room temperature is too
high

The room temperature is
higher than appropriate
temperature to work.

Adjust temperature in the
room to the appropriate
range or follow by the
manual such as to
increase flow rate air

There’s circulate hot air in the
room causes from wrong
installation

The room temperature is too
high

To change the position of
air dryer to rearrange the
surroundings to limit
circulate air

The fins of refine unit were
dirty.

At The display always show
>4 °C.

Clean the refine unit fins

Refine unit was clogged.

At The display always show

>4 °C.

Clean the refine units

Room has rather high
temperature and fan has invert
spin.( In case 3 phases used)

The cooling air had pass on
fan and refine unit.

Invert the electric phase

E

High
pressure
switch stop
working and
have to
control by
manual

The refrigerant leaked.

Temperature of the dew point

too high (Moisture might be
observed near entrance).

Check for leaking marks

Air pressure too low, inlet
temperature too high, ambient
temperature too high.

The compressor stopped
before reached the fixed
balancing point value.
Compressor restarts again
after 2-3 minutes because the
pressure is back to normal

Recommend to turn off
the machine.

F

Low pressure
Switch stops
working.

Refrigerant pressure too low,
refrigerant leak

-Top of the compressor is very
hot
Compressor stops then
restarts after 2~3 seconds.

Check for leaking marks
and refill the refrigerant

G

Prevent
compressor
shut down

High pressure switch stopped
working

-Top of the compressor is very
hot
-Compressor stopped working

Ensure the high
temperature switch is in
good condition; if not
then change a new one.