Venting installation, Warning, Caution – Harman Stove Company PB 105 User Manual

Page 13

Advertising
background image

13

3-90-07205R19_05/13

Chimneys taller than 20’ above the connection will

require a draft test to determine if the draft is too high.

Note: The high burn draft should not exceed .85 IWC.

Some form of a restrictor plate may be required at the

top of high chimneys to reduce the draft. See page 21

for the Draft Test procedure.

Creosote - Formation and Need for Removal - When wood is burned slowly, it produces tar and other organic vapors,

which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue

of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited, this creosote makes an

extremely hot fire. The pellet vent pipe should be inspected at least twice monthly during the heating season to determine

if a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney fire.

Guidance on minimizing creosote formation and the need for periodic creosote removal: The chimney should be inspected

during the heating season to determine if a creosote build-up has occurred. If a significant layer of creosote has accumulated

(3mm or more) it should be removed to reduce the risk of a chimney fire.

This boiler may be used and installed into an existing

masonry or Class A metal chimney.

Certain Canadian and Local Codes may require that

the chimney be fully relined.

The venting Can Not be installed in a chimney serving

another appliance.

The chimney should be cleaned and or inspected before

installation of the venting.

Venting Installation

NOTE: All installation clearances and restrictions

must be adhered to.

NOTE: Read and follow all of the vent pipe

manufacturers’ instructions on the proper installation

and support of the vent pipe. Adhere to all clearances.

DO NOT INSTALL A FLUE DAMPER IN THE

EXHAUST VENTING SYSTEM OF THIS UNIT.

DO NOT CONNECT THIS UNIT TO A CHIMNEY

FLUE SERVING ANOTHER APPLIANCE.

INSTALL VENT WALL PASS-THROUGHS AT

CLEARANCES SPECIFIED BY THE VENT

MANUFACTURER

INSTALLATION IS TO BE PERFORMED BY A

QUALIFIED INSTALLER.

NOTE: Use only 4” diameter approved pellet

venting system. Be sure to inspect and clean

exhaust venting system frequently.

KEEP COMBUSTIBLE MATERIALS SUCH AS

GRASS, LEAVES, ETC. AT LEAST 3 FEET AWAY

FROM THE POINT DIRECTLY UNDER THE

VENT TERMINATION. (BETWEEN THE VENT

AND THE GROUND)

WARNING

KEEP COMBUSTIBLES AWAY

FROM FLUE OUTLET.