Heat & Glo Fireplace PCFML-HNG User Manual

Page 8

Advertising
background image

8

Heat-N-Glo Lifestyles • Patio Campfi re • 4004-001 Rev D • 07/05

C. Framing Enclosure for LP Gas Supply System

If you build an enclosure for an LP gas cylinder, follow these
recommended specifi cations and local codes:

Ventilation

Enclosures must be ventilated by openings at the level of
the cylinder valve and at fl oor level. Effectiveness must be
determined with the cylinder(s) in place.

• One side of the enclosure must be completely open or,
• For an enclosure having four sides, a top and a bottom:

-

At least two ventilation openings at cylinder valve level
shall be provided in the side wall, equally sized, spaced
at 180 degrees (3.14 rad), and unobstructed. Each
opening must have a total free area of not less than
1/2 square inch per pound (3.2 sq. cm/kg) of stored
fuel capacity and not less than a total free area of 10
square inches (64.5 sq. cm).

- Ventilation opening(s) must be provided at fl oor level

and shall have a total free area of not less than 1/2
square inch per pound (3.2 sq. cm/kg) of stored fuel
capacity and not less than a total free area of 10
square inches (64.5 sq. cm). If ventilation openings
at fl oor level are in a side wall, there must be a least
two openings. The bottom of the openings must be
at fl oor level and the upper edge can’t be more than
5 in. (127 mm) above the fl oor. The openings must
be equally sized, spaced at 180 deg (3.14 rad) and
unobstructed.

- Every opening must have minimum dimensions to

permit the entrance of a 1/8 inch (3.2 mm) diameter
rod.

Accessibility

• Cylinder valves must be readily accessible for hand

operation. A door on the enclosure to gain access to the
cylinder valves is acceptable, provided it is non-locking
and can be opened without the use of tools.

• The design of the enclosure must be such that:

- The LP gas supply cylinder(s) can be connected,

disconnected and the connections inspected and
tested outside the cylinder enclosure.

- Those connections which could be disturbed when

installing the cylinder(s) in the enclosure can be leak
tested inside the enclosure.

- Be certain to mount or set the LP gas cylinder on a fl at

stable surface and retain it to prevent it from tipping.

Minimum Clearances

There must be a minimum clearance of 2 in. (50.8 mm)

between the lower surface of the fl oor of the LP gas supply
cylinder enclosure and the ground.

Advertising
This manual is related to the following products: