System test

System status

Shaded areas below apply only to

TH5320U/TH5220D

or as otherwise noted.

Press

s

/

t

to turn system on/off.

Press NEXT to advance to next test.

Press DONE to terminate system test.

Test number

System status

To begin, press and hold the

s

and

t

buttons until the display changes

Installer setup

Setup function

Settings & options (factory default in bold)

Shaded areas below apply only to

TH5320U/TH5220D

or as otherwise noted.

CAUTION: Compressor protection is bypassed during testing. To prevent equipment

damage, avoid cycling the compressor quickly

!

10

Heating system

0

Heat and fan turn off.

1

Stage 1 heat turns on. Fan turns on if Setup Function 1 is set to 1,

5, 9 or 10 OR Setup Function 3 is set to 1 **See page 6

2

Stage 2 heat turns on

3

Stage 3 heat turns on -

TH5320U

only

20

Emergency heating

system

0

Heat and fan turn off

1

Heat and fan turn on

2

Stage 2 heat turns on (auxiliary heat) -

TH5220D

only

30

Cooling system

0

Compressor and fan turn off

1

Compressor and fan turn on

2

Stage 2 compressor turns on

40

Fan system

0

Fan turns off

1

Fan turns on

9

Stage 1 compressor

cycle rate (CPH)

3

Recommended for most compressors

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

10

Stage 2 compressor

cycle rate (CPH)

3

Recommended for most compressors

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

12

Manual/Auto

changeover

0

Manual changeover (Heat/Cool/Off)

1

Auto changeover (Heat/Cool/Auto/Off)

2

Auto changeover only (Auto)

14

Temperature

display

0

Fahrenheit

1

Celsius

15

Compressor

protection

5

Five-minute compressor off time

[Other options: 0, 1, 2, 3 or 4-minute off time]

26

Auxiliary heat control

0

Comfort **See page 8

1

Economy

27

Heat temperature

range stops

90 Max. heat temperature setting is 90 °F (32 °C)

[Other options: 40 °F to 89 °F (4.5 °C to 31.5 °C)]

28

Cool temperature

range stops

50 Min. cool temperature setting is 50 °F (10 °C)

[Other options: 51 °F to 99 °F (10.5 °C to 37 °C)]