Sg series, Ups plus – Falcon SG2K-1T User Manual

Page 25

Advertising
background image

SG Series

TM

UPS PLUS

®

800VA to 1.5kVA

Model Number

SG800-1T

SG1K-1T

SG1K-2T

SG1.5K-1T

Nominal VA

800

1000

1000

1500

Electrical Input

Nominal AC Voltage

120V

120V

230V

120V

AC Voltage Range

87-140V

87-140V

170-275V

87-140V

Current -Amps

5.5

6.9

3.6

10.7

Frequency

50/60 Hz ± 5% (Auto – Tracking)

Power Factor Correction

> 0.95

Efficiency (Typical)

> 86%

Electrical Output

Watts

560

700

700

1050

AC Voltage
(Switchable )

100V
110V
115V
120V

100V
110V
115V
120V

200V
220V
230V
240V

100V
110V
115V
120V

Frequency

50/60 Hz (Auto Tracking )

Frequency Stability

±0.3% (Battery Mode)

Voltage Regulation

± 2%

Step Load Change

± 7% for 100% load variation

Harmonic Distortion

< 3% Linear Load, < 5% Non -Linear Load

Overload

105% load for 50 Seconds

Crest Ratio

3:1

Battery

DC Voltage

36V

72V

Type

12V, 7AH Sealed Lead Acid Maintenance -Free

Back Up Time @ Full Load

@ 1/2 Load

9 Minutes

25 Minutes

6 Minutes

19 Minutes

11 Minutes
30 Minutes

Recharge Time

8 Hours to 90%

Battery times are approximate.

Transfer Time

Line Fails/Recovers

Zero

UPS to Bypass or Reverse

< 4ms

After Overload

Auto Transfer to UPS

Electrical Connections

Input

6’ Cord with

5-15P

6’ Cord with

5-15P

6’ Cord with

Schuko or 6 -15P

6’ Cord with

5-15P

Output

(6) 5-15R

(6) 5-15R

(4) IEC 320

(6) 5-15R

Contact the factory for other input/output options.

Environmental

Operating Temperature

0º C - 40º C (32º F to 104º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noi se @ 1 Meter

<45dBA

< 50dBA

Controls and Indicators

LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery

& Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp. , Over Load, Fau lt Alarm

Communications

RS-232 Serial Port (Bundled UPSilon 2000 Software)

Mechanical

Dimensions H x W x D inches
(mm)

8.7 x 6.0 x 15.8

(220.9 x 152.4 x 401.3)

13.8 x 7.6 x 18.9

(350.5 x 193.0 x 480 .0)

Weight lb. (kg )

33 (14.9)

68 (30.9)

Agency Listing

UL 1778 , CUL,

FCC Class A

CE

available with Schuko

plug only

UL 1778 , CUL,

FCC Class A

Available Options

Option A

60 Hz to 50 Hz Frequency Conversion

Option B

50 Hz to 60 Hz Frequency Conversion

Option C

SNMP/HTTP Network Card (Internal)

Option D

Standard Contact Closure Interface Card

Maintenance Bypass

Make-Before-Break External Wrap Around

External Battery Packs

Extended Run Time Battery Packs (minut es to hours)

Fast Battery Charger

Fast Charger internal to the Extended Battery Pack Cabinet (Required for battery times 2 hours or more.)

23

Advertising
This manual is related to the following products: