INSTALLATION

Continued

Figure 15 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff
Valve

Figure 16 - Checking Gas Joints

Control Valve
Location

Propane/LP
Supply Tank

Equipment
Shutoff
Valve

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2
psig will damage heater regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

4.

Check all joints of gas supply piping
system. Apply a noncorrosive leak de-
tection fluid to gas joints. Bubbles
forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 15).

2.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

3.

Check all joints from propane/LP sup-
ply tank to equipment shutoff valve (see
Figure 16). Apply a noncorrosive leak
detection fluid to gas joints. Bubbles
forming show a leak.

4.

Correct all leaks at once.

Pressure Testing Heater Gas
Connections

1.

Open equipment shutoff valve (see Fig-
ure 15).

2.

Open propane/LP supply tank valve.

3.

Make sure control knob of heater is in
the OFF position.

4.

Check all joints from equipment shutoff
valve to control valve (see Figure 16).
Apply a noncorrosive leak detection
fluid to gas joints. Bubbles forming
show a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater,
pages 15 and 16). Check all other in-
ternal joints for leaks.

7.

Turn off heater (see To Turn Off Gas to
Appliance
, page 16).

WARNING: Never use an open

flame to check for a leak. Apply a
noncorrosive leak detection fluid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.

WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed
between propane/LP supply and
heater. See guidelines under

Con-

necting to Gas Supply, page 12.

CHECKING GAS
CONNECTIONS

Continued