Ed series, Uvs plus, Model -a – Falcon ED3000-A User Manual

Page 16

Advertising
background image

ED Series

TM

UVS PLUS

®

Model -A

ED Series Model -A Frequency Converter (120V Input/Output)

Model Number

ED-1000-A

ED-1500-A

ED-2000-A

ED-3000-A

ED-4000-A

Nominal VA

1000

1500

2000

3000

4000


Electrical Input

AC Voltage, +10% -20%

120V

120V

120V

120V

120V

Current-Amps

10.4

15.6

20.8

29

39

Frequency Range

47 – 450

47 - 450

47 - 450

47 - 450

47 - 450


Electrical Output

AC Voltage, ± 3%

120V

120V

120V

120V

120V

Watts @ 50 or 60 Hz

700

1050

1400

2100

2800

Watts @ 400 Hz (-400 option)

595

892

1190

1785

2380

Current-Amps @ 50/60 Hz

8.3

12.5

16.7

25

33

Current-Amps @ 400Hz

7.1

10.6

14.2

21.3

28

50/60 Hz Non – Linear
Repetitive Peak (Amps)

20

30

40

60

80

400 Hz Non – Linear
Repetitive Peak (Amps)

14.2

21.3

28.3

42.5

56

Total Harmonic Distortion

< 3% @ 100% Linear Load, < 5% @ 100% Non – Linear Load

Overload

200% for 0.5 Seconds, 120% for 30 Seconds

Dynamic Response

± 5% RMS for 100% Step Load Change, 1ms Recovery Time

Output Protection

Short Circuit and Overload


Electrical Connections

Input

6’ Cord with

5-15P

8’ Cord with

5-20P

8’ Cord with

L5-30P

Hardwired

Hardwired

Output

(4) 5-15R

(4) 5-15R

(4) 5-15R

Hardwired

Hardwired


Environmental

Operating Temperature

0º C to 35º C (32º F to 95º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1.5 Meters

49dBA

54dBA


Controls and Indicators

Sequenced LEDs

Load Level

Single LED

Utility Present, Summary Alarm, Inverter On

Audible Alarms

Utility Interrupt, Inverter Failure, Overload

Communications

Dry Contact Closures on Utility Loss via 9 Pin “D” Connector


Mechanical

Dimensions H x W x D inches (mm)

13.5 x 6.25 x 19.4 (342.9 x 158.8 x 492.8)

Weight lb. (kg)

25 (11.3)

38 (17.2)

38 (17.2)

50 (22.7)

50 (22.7)

Specify input/output frequency, 50/60 or 400Hz (any combination).
Standard models shown. Custom configurations available; Consult Factory.

Note: For ED3000-A and ED4000-A models add a -400 to the end of the model number for a
400Hzoutput