SG Series

TM

UPS PLUS

®

1kVA to 3kVA

22

Model Number

SG1KRM -1TU

SG1KRM -2TU

SG2KRM -1TU

SG2KRM-2TU

SG3KRM-1TU

SG3KRM-2TU

Nominal VA

1000

2000

3000

Electrical Input
Nominal AC Voltage

120V

230V

120V

230V

120V

230V

AC Voltage Range

87-140V

170-275V

87-140V

170-275V

87-140V

170-275V

Current-Amps

6.9

3.6

14.2

7.5

21.4

11.2

Frequency

50/60 Hz ± 5% (Auto–Tracking)

Power Factor Correction

> 0.95

Efficiency (Typical)

> 89%

> 86%

Electrical Output
Watts

700

700

1400

1400

2100

2100

AC Voltage
(Switchable )

100V
110V
115V
120V

200V
220V
230V
240V

100V
110V
115V
120V

200V
220V
230V
240V

100V
110V
115V
120V

200V
220V
230V
240V

Frequency

50/60 Hz (Auto Tracking )

Frequency Stability

± 0.3% (Battery Mode)

Voltage Regulation

± 2%

Step Load Change

± 7% for 100% load variation

Harmonic Dis tortion

< 3% Linear Load, < 5% Non -Linear Load

Overload

105% load for 50 Seconds

Crest Ratio

3:1

Battery
DC Voltage

48V

72V

96V

Type

12V, 7AH Sealed Lead Acid Maintenance -Free

Back Up Time @ Full Load

@ 1/2 Load

6 Minutes

19 Minutes

7 Minutes

20 Minutes

5.5 Minutes

15 Minutes

Recharge Time

8 Hours to 90%

Battery times are approximate.

Transfer Time
Line Fails/Recovers

Zero

UPS to Bypass or Reverse

< 4ms

After Overload

Auto Transfer to UPS

Electrical Connecti ons
Input

6’ Cord with

5-15P

6’ Cord with

Schuko or

6-15P

6’ Cord with

L5-20P

6’ Cord with

Schuko or

6-15P

6’ Cord with

L5 -30P

6’ Cord with

Schuko or

L6-20P

Output

(4) 5-15R

(4) IEC320

(4) 5-15R

(4) IEC 320

(4) 5-15R

(4) IEC 320

Contact the factory fo r other input/output options. .

Environmental
Operating Temperature

0º C - 40º C (32º F to 104º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 Meter

< 55dBA

Controls and Indicators
LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery

& Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp. , Over Load, Fault Alarm

Communications

RS-232 Serial Port (Bundled UPSilon 2000 Software)

Mechanical
UPS Module Dimensions
Battery Pack Dimensions

H x W x D Inches (mm)

3.51 x 16.8 x 17.7 (89 x 426.7 x 449.5)

Internal to UPS Module

3.51 x 16.8 x 17.7 (89 x 426.7 x 449.5)

3.51 x 16.8 x 17.7 (89 x 4 26.7 x 449.5) External to UPS Module

2kVA & 3 kVA are (2) cabinet configuration, Hot Swappable Batteries

UPS Module Weight lb. (kg)

Battery Pack Weight lb. (kg)

39 (18)

Internal

29 (13)

53 (24)

29 (13)
64 (29)

Agency Listing

UL 1778, CU L,

FCC Class A

CE

available with

Schuko plug only

UL 1778, CUL,

FCC Class A

CE

available

with Schuko

plug only

UL 1778, CUL,

FCC Class A

CE

available

with Schuko

plug only

www.falconups.com - email: [email protected]

©

2003 Falcon

®

Electric, Inc. All rights reserved. Falcon

®

and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.

All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice.

MD44010-1F 08-05-03

Available Options

Option A

60 Hz to 50 Hz Frequency Conversion

Option B

50 Hz to 60 Hz Frequency Conversion

Option C

SNMP/HTTP Network Card (Internal)

Option D

Standard Contact Closure Interface Card

External Battery Packs

Extended Run Time Battery Packs (minutes to hours)

Slide Rails

Heavy Duty Roller Bearing Slide Rails for side mounting

Falcon Electric, Inc. - 5116 Azusa Canyon Rd. - Irwindale, CA91706 - 800.842.6940 Fax 626.962.7720