1.0

UPS Input & Output Requirements.

Note: All SG Series hardwire UPS models must be installed by a licensed
electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70
and all local regulations. It is further required that the input of SG Series hardwire
UPS be wired to a building service panel incorporating a dedicated “branch
rated” circuit breaker of the proper rating.

MODEL

REQUIRED

BRANCH RATED

CIRCUIT BREAKER

SG2K-1T-HW:- 120Vac, 50/60Hz, 14.2A, 1 phase, 2 wire plus ground

20A

SG2K-2T-HW - 208-240Vac, 50/60Hz, 7.4A, 1 phase, 2 wire plus ground

15A

SG3K-1T-HW - 120Vac, 50/60Hz, 21.4A, 1 phase, 2 wire plus ground

30A

SG3K-2T-HW - 208-240Vac, 50/60Hz, 11.2A, 1 phase, 2 wire plus ground

20A

WIRE GAUGE CHART

MODEL

AC INPUT

-1 = 120 Vac

-2 = 208-240 Vac

AC OUTPUT(S)

120 Vac 208 -240 Vac

SG2K-1T-HW

10 Awg. 600V

75

°C CU

10 Awg. 600V

75

°C CU

N/A

SG2K-2T-HW

12 Awg. 600V

75

°C CU

N/A

12 Awg. 600V

75

°C CU

SG3K-1T-HW

10 Awg. 600V 75

°C

CU

10 Awg. 600V

75

°C CU

SG3K-2T-HW

12 Awg. 600V

75

°C CU

12 Awg. 600V

75

°C CU

SCREW TORQUE SPECIFICATIONS FOR

INPUT/OUTPUT WIRING BLOCK

UPS

Wire Gauge

Torque

(inch pounds)

18 - 10 Awg.

20

8-6 Awg

25 - 30

ONLY USE WIRE WITH SOLID COPPER CONDUCTORS FOR ALL INPUT/OUTPUT/BATTERY WIRING

CAUTION

To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the

specified "branch rated" over-current protection device in accordance with the National Electrical

Code, ANSI/NFPA 70.