Falcon F3400 User Manual

Page 38

Advertising
background image

www.rletech.com

38

970.484.6510

4

Configuration Menu

Example: Temperature sensor with a sensing range of 50-95°F - displayed in Fahrenheit

Gain = (95-50) / 4 = 11 (round to the nearest integer)

Offset = 50 - 11 = 39

Example: Temperature sensor with a sensing range of 50-95°F - displayed in Celsius

Convert 50-95°F to 10-35°C and use the Celsius range for the calculations

Gain = (35-10) / 4 = 6 (round to the nearest integer)

Offset = 10 - 6 = 4

Example: Humidity sensor with a range of 0 - 100% RH

Gain = (100-0) / 4 = 25

Offset = 0 - 25 = -25

High Limit 2: Applies only when the input type is Analog 4-20mA. The F3400/F1000 will

record an alarm and send notification when the F3400/F1000's calculated value exceeds this

limit. The High Limit 1 and High Limit 2 are disabled when they are both set to 0.

High Limit 1: Applies only when the input type is set for Analog 4-20mA. The F3400/F1000

will record an alarm and send notification when the F3400/F1000’s calculated value exceeds

this limit. The High Limit 1 and High Limit 2 are disabled when they are both set to 0.

Low Limit 1: Applies only when the input type is Analog 4-20mA. The F3400/F1000 will

record an alarm and send notification when the F3400/F1000's calculated value falls below this

limit. The Low Limit 1 and Low Limit 2 are disabled when they are both set to 0.

Low Limit 2: Applies only when the input type is Analog 4-20mA. The F3400/F1000 will

record an alarm and send notification when the F3400/F1000's calculated value falls below this

limit. The Low Limit 1 and Low Limit 2 are disabled when they are both set to 0.

Unit Of Measure (UOM): The 10 character field used to assign a unit of measure label to

analog values, such as °F, °C, % RH, Amps, Volts, PSI, etc. The unit of measure field is only

required when the input type is Analog 4-20mA. The unit of measure field is displayed on the

Main Menu and in notification (email/pager messages and SNMP Trap).

Alarm Label: Used for input identification. Applies to all input types except “Not Configured”.

For Analog input types, this label is displayed on the F3400/F1000 Main Menu and the Input

Configuration Menu. When the input alarms and/or returns to normal, the label is included in

the Alarm History and notification messages. For Digital NO and Digital NC inputs, the label is

displayed on the F3400/F1000 Main Menu, Input Configuration Menu, Alarm History page and

in notification messages only when the device is in alarm. For Digital Status inputs, the label is

displayed on the F3400/F1000 Main Menu when the input is on. When the input turns on, the

label is also included in the Digital Status History.

Normal Label: Applies to input types Digital NO, Digital NC and Digital Status. This field

may be left blank. If it is left blank, the F3400/F1000 displays the Label (from above). This

label is displayed on the main page when the input is normal, in the Alarm History when the

input returns to normal and in notification messages. For Digital Status inputs, the label is

displayed on the main page when the input is off. When the input turns off, the label is also

included in the Digital Status History.

Advertising
This manual is related to the following products: