Frymaster ELECTRIC SERIES OCF30 User Manual

Page 11

Advertising
background image

2-3

2.1.3 Australian Requirements

To be installed in accordance with AS 5601, local authority, gas, electricity, and any other relevant
statutory regulations.

2.2 Power

Requirements

Three (3) Phase Requirements

MODEL VOLTAGE

WIRE

SERVICE

MINIMUM WIRE

SIZE

AWG (mm)

AMPS

(per leg)

FPEL14 208 3

6

(4.11)

39

FPEL14 240 3

6

(4.11)

34

FPEL14 480 3

8

(2.59)

17

FPEL14 220/380 4 6

(4.11)

21

FPEL14 240/415 4 6

(4.11)

20

FPEL14 230/400 4 6

(4.11)

21

FPEL17 208 3

6

(4.11)

48

FPEL17 240 3

6

(4.11)

41

FPEL17 480 3

6

(4.11)

21

FPEL17 220/380 4 6

(4.11)

26

FPEL17 240/415 4 6

(4.11)

24

FPEL17 230/400 4 6

(4.11)

25


NOTICE

If this appliance is permanently connected to fixed wiring, it must be connected by
means of copper wires having a temperature rating of not less than 167°F (75°C).

DANGER

This appliance must be connected to a power supply having the same voltage and
phase as specified on the rating plate located on the inside of the appliance door.

DANGER

All wiring connections for this appliance must be made in accordance with the
wiring diagram(s) furnished with the appliance. Refer to the wiring diagram(s)
affixed to the inside of the appliance door when installing or servicing this
equipment.