2

Mounting

This unit does not have power switch. If you
do not connect the IF-2500 to power
switchboard or circuit breaker, install an
external power switch (local supply), locating
it near the IF-2500.

All dimensions in millimeters.

For added support, use nuts, bolts and

washers instead of woodscrews.

Leave sufficient space at the sides and rear

of the unit for maintenance and servicing.

Grounding

To prevent mutual interface, run a ground
wire between the earth terminal on the unit
and ship’s superstructure.

Selection of output data format

The output data format is selectable by
changing a jumper block; A for IEC61162-1
and B for NMEA. For example, to select
NMEA for J4, change the jumper block from A
to B on JP401 and JP402. Do the same on J5
thru J9.

Factory setting

Output

Jumper

IEC61162-1

(A)

Current

loop

(B)

J4 JP401/JP402

!

J5 JP501/JP502

!

J6 JP601/JP602

!

J7 JP701/JP702

!

J8 JP801/JP802

!

J9 JP901/JP902

!

Cable fabrication

Use the following cables (Japan Industrial
Standard cables) or the equivalents.

Conductor
S = 0.75 mm

φ

= 1.11 mm

2

TTYCS-1 (Twisted pair cable)

Conductor
S = 0.2 mm

φ

= 0.6 mm

2

CO-SPEVV-SB-C 0.2x2P

Armor

Armor

Vinyl sheath

Shield

Shield

Sheath

Sheath

Current loop or IEC 61162-1 signal

Current loop or IEC 61162-1 signal

φ

=

10.1 mm

φ

=

10.5 mm