Table 1. Specifications

Actuator Sizes and Maximum Casing Pressures

ACTUATOR

MAXIMUM CASING PRESSURE

ACTUATOR

SIZE

Bar

Psig

3A, 4A

17.2

250

3B, 4B

12.1

175

32, 42

6.9

100

33, 43

4.5

65

34, 44

3.1

45

35, 45

2.1

30

36, 46

1.0

15

Actuator Pressure Setting Ranges

See table 2

Actuator Yoke Boss and Valve Stem Connection
Diameters

Sizes 3A through 36: 54 mm (2-1/8 inch) yoke
boss with 9.5 mm (3/8 inch) stem connection
Sizes 4A through 46: 71 mm (2-13/16 inch) yoke
boss with 12.7 mm (1/2 inch) stem connection

Maximum Travel

Sizes 3A and 4A: 11 mm (0.4375 inch) plus
3 mm (0.125 inch) for seating

All Other Sizes: 19 mm (0.75 inch) plus 3 mm
(0.125 inch) for seating

Effective Diaphragm Area

See table 3

Spring Rate

See key 6 in the parts list section

Temperature Capabilities

–29 to 82

_C (–20 to 180_F) with standard

diaphragm material. For the fluid and temperature
capabilities of nonstandard diaphragm materials,
consult your Emerson Process Management
sales office

Casing Pressure Connections

1/2 NPT internal

Approximate Weights

ACTUATOR

APPROXIMATE WEIGHT

ACTUATOR

SIZE

Kg

Lb

3A, 3B, 32, 33

20

45

34, 35, 36

23

50

4A, 4B, 42, 43

29

65

44, 45, 46

34

75

Specifications

Specifications for the Type 655 and 655R actuators
are shown in table 1. Information for a specific
actuator is also found on the nameplate of that
actuator.

Installation

WARNING

To avoid personal injury or property
damage caused by bursting of
pressure-retaining parts, be certain the
service conditions do not exceed the
casing pressure limits listed in table 1.
Use pressure-limiting or
pressure-relieving devices to prevent
service conditions from exceeding
these limits.

Always wear protective gloves,
clothing, and eyewear when
performing any installation operations
to avoid personal injury.

Check with your process or safety
engineer for any additional measures
that must be taken to protect against
process media.

If installing into an existing
application, also refer to the WARNING
at the beginning of the Maintenance
section in this instruction manual.

Type 655 and 655R actuators are normally shipped
mounted on a valve. Refer to the appropriate valve
instruction manual when installing the valve in the
pipeline. If the actuator is shipped separately or if it
is necessary to mount the actuator on the valve,
perform the procedures described in the Actuator
Mounting portion of this section.