18–2

MULTILINK ML1600 ETHERNET COMMUNICATIONS SWITCH – INSTRUCTION MANUAL

MODBUS CONFIGURATION

CHAPTER 18: MODBUS PROTOCOL

The commands enable the Modbus protocol and set the relevant Modbus slave address
and communication port values.

For example,

ML1600#

show ipconfig

IP Address:

192.168.1.5

Subnet Mask:

255.255.255.0

Default Gateway: 192.168.1.10

ML1600#

show modbus

Access to Modbus disabaled

Modbus is Using Port: 502

Modbus is Using Device: 5

ML1600#

access

ML1600(access)##

modbus enable

Enabling Access to Modbus

ML1600(access)##

show modbus

Access to Modbus enabled

Modbus is Using Port: 502

Modbus is Using Device: 5

ML1600(access)##

modbus port=602

Modbus Port is set

ML1600(access)##

show modbus

Access to Modbus enabled

Modbus is Using Port: 602

Modbus is Using Device: 5

ML1600(access)##

modbus port=default

Modbus Port Set to Default

ML1600(access)##

show modbus

Access to Modbus enabled

Modbus is Using Port :502

Modbus is Using Device :5

18.1.3 EnerVista Settings