GENERATOR OUTPUT VOLTAGE/KW-60Hz

Rated AMP

Rated AMP

120/240V, 1-phase, 1.0 pf

100

417

91

379

120/208V, 3-phase, 0.8 pf

100

347

91

316

120/240V, 3-phase, 0.8 pf

100

301

91

274

277/480V, 3-phase, 0.8 pf

100

150

91

137

600V, 3-phase, 0.8 pf

100

120

91

109

MOTOR STARTING KVA
Maximum at 35% instantaneous voltage dip

208/240/416V

480V

208/240/416V

480V

with standard alternator; 60 Hz

206

275

206

275

FUEL
Fuel consumption—60 Hz

Load

25%

50%

75%

100%

25%

50%

75%

100%

gal./hr.

2.3

4.3

5.9

7.7

1.9

3.5

5.1

6.3

liters/hr.

8.7

16.2

22.4

29.0

7.1

13.3

19.4

23.9

Fuel consumption—50 Hz

gal./hr.

1.8

3.4

4.7

6.1

1.5

2.8

4.1

5.0

liters/hr.

7.0

12.9

17.9

23.2

5.7

10.6

15.5

19.1

Fuel pump lift

36"

36"

COOLING
Coolant capacity

System - US gal. (lit.)

5.5 (20.8)

5.5 (20.8)

Engine - US gal. (lit.)

3.75 (14.2)

3.75 (14.2)

Coolant flow/min.

60 Hz - US gal.

38

38

Heat rejection to coolant 60 Hz full load BTU/hr.

280,000

252,000

Inlet air*

60 Hz - cfm (m

3

/min.)

7500 (212.4)

7500 (212.4)

Max. air temperature to radiator*

° C (°F)

60 (140)

60 (140)

Max. operating ambient temperature* °C (°F)

50 (122)

50 (122)

COMBUSTION AIR REQUIREMENTS
Flow at rated power

60 Hz - cfm (m

3

/min.)

351 (10.0)

320 (9.1)

EXHAUST
Exhaust flow at rated output 60 Hz - cfm (m

3

/min.)

988 (28.0)

880 (24.9)

Max recommended back pressure

Inches Hg

1.5

1.5

Exhaust temperature 60 Hz (full load) °F (°C)

1050 (566)

990 (532)

Exhaust outlet size

4.0" O.D.

4.0" O.D.

ENGINE
Rated RPM

60 Hz

1800 / 1500

1800

HP at rated KW

60 Hz

158 / 122

144 / 99

Piston speed

60 Hz - ft./min. (m/min.)

1500 (457)

1500 (457)

BMEP

60 Hz / psi

248

225


DERATION FACTORS
Temperature

-4.1% for every 10

o

C above - °C

40

40

-2.3% for every 10

o

F above - °F

104

104

Altitude

-0.8% for every 100 m above - m

1067

1067

-2.5% for every 1000 ft. above - ft.

3500

3500

OPERATING DATA

NOTE: Consult your
Generac dealer for
additional voltages.

SD100

* Note: Values given are maximum temperatures to which power adjustments can be applied. Consult your Generac

Power Systems representative if operating conditions exceed these maximums.