Installation instructions - continued, Table 8 input and output terminal specifications – GE SERIES B 480 User Manual

Page 33

Advertising
background image

INSTALLATION INSTRUCTIONS - continued

GEH-7252

30

May 2003

g

GE Capacitor & Power Quality Products

Table 8

Input and Output Terminal Specifications

Filter

Rating(Amps)

Input Terminals

Output Terminals

Wire Range

(AWG)

Terminal Torque

(in-lbs)

Wire Range

(AWG)

Terminal Torque

(in-lbs)

6

22 -14

4.5

22 – 14

4.5

8

11

22 - 14

4.5

22 – 14

4.5

14

22 - 14

4.5

22 – 5

16

21

22 - 5

16

22 – 5

16

27

22 - 5

16

22 – 5

16

34

22 - 5

16

18 – 4

20

44

22 - 5

16

18 – 4

20

52

18 – 4

20

18 – 4

20

66

18 – 4

20

6-4
2-0

45
50

83

6-4
2-0

45
50

6-4
2-0

45
50

103

6-4
2-0

45
50

6-4
2-0

45
50

128

6-4
2-0

45
50

6-4
2-0

45
50

165

6-4
2-0

45
50

2-0000

150

208

2 – 0000

150

2 – 0000

150

240

2 – 0000

150

2 – 0000

150

320

2-0000

150

00

000-0000

250-350 MCM

500 MCM

180
250
325
375

403

00

000-0000

250-350 MCM

500 MCM

180
250
325
375

00

000-0000

250-350 MCM

500 MCM

180
250
325
375

482

00

000-0000

250-350 MCM

500 MCM

180
250
325
375

00

000-0000

250-350 MCM

500 MCM

180
250
325
375

636

NA

NA

NA

NA

786

NA

NA

NA

NA

Advertising