10 specifications, 11 fuel consumption, 12 reconfiguring the fuel system – Generac 0047210 User Manual

Page 9: Figure 1.8 — reconfigure the fuel system

Advertising
background image

1.10 SPECIFICATIONS

1.10.1 GENERATOR SPECIFICATIONS

1.10.2 ENGINE SPECIFICATIONS

Make ..............................................................................Mitsubishi
Displacement ..............................................92 inches

3

(1.5 liters)

Cylinder Arrangement......................................................4, in-line
Valve Arrangement................................................Overhead Cam
Firing Order........................................................................1-3-4-2
Number of Main Bearings............................................................5
Compression Ratio ..............................................................9 to 1
No. of Teeth on Flywheel ........................................................104
Ignition Timing

at 1800 rpm ..................................................35 degrees BTDC
at 3600 rpm ..................................................43 degrees BTDC

Spark Plug Gap ..................................................0.020-0.025 inch
Recommended Spark Plugs

Champion ....................................................................RN11YC4

Oil Pressure....................................................................30-50 psi
Crankcase Oil Capacity........................3.0 U.S. quarts (2.8 liters)
Recommended Engine Oil........................................SAE 15W-40
Type of Cooling System ..................Pressurized, closed recovery
Cooling Fan ..............................................................Pusher Type
Cooling System Capacity ......................2 U.S. gallons (7.6 liters)
Recommended Coolant ............................Use a 50-50 mixture of

ethylene glycol base.

1.11 FUEL CONSUMPTION

25 kW Models

Using Natural Gas ........................................441 cu. ft. per hour
Using LP Gas ..............................175 cubic ft.(4.8 gal.) per hour

20 kW Models

Using Natural Gas ........................................359 cu. ft. per hour
Using LP Gas ............................143 cubic ft. (4.0 gal.) per hour

15 kW Models

Using Natural Gas ........................................277 cu. ft. per hour
Using LP Gas ..............................110 cubic ft.(3.1 gal.) per hour

NOTE:

Fuel consumption is given at rated maximum con-
tinuous power output when using natural gas
rated at 1000 Btu per cubic foot and LP gas rated
2520 Btu per cubic foot. Actual fuel consumption
obtained may vary depending on such variables as
applied load, ambient temperature, engine condi-
tions and other environmental factors.

Fuel pressure for both natural gas and liquid
propane set ups should be 11 inches to 14 inches
of water column (0.6 psi) at all load ranges.

NOTE:

A seperate gas line and regulator may be needed
to assure proper gas pressure (11-14”) to the gen-
erator. Low gas pressure can cause hard starting
and could affect engine durability.

1.12 RECONFIGURING THE FUEL

SYSTEM

NOTE:

All models are configured for natural gas from the
factory.

To reconfigure the fuel system from NG to LP, follow
these steps:

1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet

port (Port 1) of the demand regulator (Figure
1.8).

3. Remove the brass hose fitting from the outlet port

(Port 1) of the demand regulator.

4. Remove pipe plug from Port 2.
5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure

and type for configuration.

10. Reverse the procedure to convert back to natural

gas.

Figure 1.8 — Reconfigure the Fuel System

NG FUEL SYSTEM

LP FUEL SYSTEM

Port 1

Port 2

FUEL HOSE

BRASS HOSE
FITTING

HOUSING
PORTS

OUT
PORT 2

PLUG

FUEL HOSE

BRASS HOSE
FITTING

HOUSING
PORTS

PLUG

OUT

PORT 1

‹

‹

Section 1 — General Information

Guardian Liquid-cooled 15 kW, 20 kW and 25 kW Generators

Generac

®

Power Systems, Inc.

7

Single-Phase

Model

004725 004723 004721
004726 004724 004722

Rated Max. Cont.

25

20

15

AC Power Output (kW)
Rated voltage (volts)

120/240

No. of Rotor Poles

2

4

Driven Speed of Rotor

3600

3600

1800

Rotor Excitation System

Direct excited brush type

Type of Stator

4 Wire

Rotor/Stator Insulation

Class F

Advertising
This manual is related to the following products: