6 setting the exercise timer, Danger – Generac 004692-2 User Manual

Page 17

Advertising
background image

Generac

®

Power Systems, Inc.

15

Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

4. Use the manual transfer handle inside the trans-

fer switch to move the main contacts to their
“Standby” position, i.e., loads connected to the
standby power source (Figure 3.2).

5. To crank and start the engine, set the

AUTO/OFF/MANUAL switch to MANUAL.

6. Let the engine stabilize and warm up for a few

minutes.

7. Set the generator’s main circuit breaker to its ON

(or closed) position. The standby power source
now powers the loads.

Figure 3.2 – Manual Transfer Switch Operation

3.5.2 TRANSFER BACK TO UTILITY POWER

SOURCE

When utility power has been restored, transfer back
to that source and shut down the generator. This can
be accomplished as follows:

1. Set the generator’s main circuit breaker to its

OFF (or open) position.

2. Let the engine run for a minute or two at no-load

to stabilize the internal temperatures.

3. Set the generator’s AUTO/OFF/MANUAL switch to

its OFF (or open) position. The engine should
shut down.

4. Check that UTILITY power supply to the transfer

switch is turned OFF.

Do not attempt to activate the transfer switch
manually until all power voltage supplies
to the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.

5. Use the manual transfer handle inside the trans-

fer switch to move the main contacts back to their
UTILITY position, i.e., loads connected to the
UTILITY power source (Figure 3.2).

6. Turn ON the UTILITY power supply to the trans-

fer switch using the means provided.

7. Set the system to automatic operation as outlined

in “Automatic Transfer Operation,” Section 3.3.

3.6

SETTING THE EXERCISE TIMER

The generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise
once every seven days, on the day of the week and at
the time of day the following sequence is completed.
During this exercise period, the unit runs for approx-
imately 12 minutes and then shuts down. Transfer of
loads to the generator output does not occur during
the exercise cycle.

A switch on the control panel (see Figure 3.1) permits
selection of the day and time for system exercise. To
select the desired day and time of day, the following
sequence must be performed at that time.

1. Verify that the AUTO/OFF/MANUAL switch is set

to AUTO.

2. Hold down the “Set Exercise Time Switch” until

the generator starts (approximately 10 seconds)
and then release. During this time all the red
LEDs on the control panel will flash to indicate
board is resetting itself.

3. The generator will start and run for approximately

12 minutes and then shut down on its own. The
exerciser will then be set to run at that time of day
every week.

NOTE:

The exerciser will only work in the AUTO mode
and will not work correctly unless this procedure
is performed. The exerciser will need to be reset
every time the 12-volt battery is disconnected and
then reconnected. The exerciser WILL NOT work
if dip switch 2 on the controller printed circuit
board (“Remote Not Auto”) is ON.

If the exerciser is not set using the “Set Exercise
Time Switch”, the generator will automatically
exercise 7 days after the battery connection was
made.

DANGER

‹

DANGER

Section 3 — Operation

Air-cooled 8.5 kW Generator

Advertising