Model G0637

440V Conversion

The Model G0637 can be rewired for 440V opera-
tion. This rewiring job consists of disconnecting
the dust collector from the power source, chang-
ing the control box, and rewiring the motor.

The necessary control box for this procedure can
be purchased by calling our customer service
number at (800) 523-4777 and ordering part num-
ber P0637119.

When complete, the rewiring job must be inspect-
ed by a qualified electrician before the dust collec-
tor is connected to the power source. Refer to the

Wiring Diagrams on Pages 45–46 for additional
information.

Model G0638

440V Conversion

To operate the Model G0638 on 440V power, you
must purchase a G0638 440V Conversion Kit.
Call our customer service number at (800) 523-
4777 and order part number P0638119.

To convert the G0638 to 440V:

1. DISCONNECT THE DUST COLLECTOR

FROM THE POWER SOURCE!

2. Open the control box and identify the over-

load relay and the transformer (see

Figure

3).

Figure 3. Model G0638 control box overload

relay and transformer.

Transformer

Overload

Relay

3. Replace the overload relay with the one

included in the conversion kit, and turn the
AMP dial to 15.

4. Move the "R0" wire on the transformer from

the 220V terminal to the 440V terminal (see

Figure 4).

���� ���� ����

���� ����

�����������

��

��

��

���������������

���������������

��

��

����

Figure 4. Model G0638 220V and 440V

transformer connections.

5. Open the motor junction box and rewire the

motor terminals for 440V power. Refer to

Wiring Diagram on Page 48 for additional
information.

You must have a qualified electrician inspect

your 440V rewiring job before connecting

the dust collector to the power source.

Failure to heed this warning may result in

property damage, serious personal injury, or

death from electrocution.