Gas-Fired Products Space-Ray ETU Series User Manual

Page 3

Advertising
background image

MODEL

ETS AND ETU

DRAFT INDUCER

CONTROL BOX

Flue Connection:

4” Round for ETS/U (40-75)
6” Round for ETS/U (80-250)

Fresh Air Connection:

4” Round for ETS/U (40-75)
6” Round for ETS/U (80-250)

ETS OPTIONS

90° ELBOW

CORNER REFLECTOR

ETS - BOTTOM VIEW

ETS - END VIEW

DIMENSIONS

MINIMUM RECOMMENDED MOUNTING HEIGHTS

MINIMUM CLEARANCES TO COMBUSTIBLES

ETU - BOTTOM VIEW

ETU - END VIEW

TOTAL TUBE

OVERALL

LENGTH (FT)

DIMENSION”L”(FT)

DESIGN

CERTIFIED

TOTAL TUBE

OVERALL

LENGTH (FT)

DIMENSION ”L” (FT)

MODEL

ETS (40, 50)

ETS (40, 50, 60, 75)

ETS (40, 50, 60, 75, 80, 90,
100, 110, 120, 130)

ETS (80, 90, 100, 110, 120,
125, 130, 140, 150, 160,175)

ETS (125, 130, 140, 150,
160, 175, 180, 200, 225, 250)

ETS (180, 200, 225, 250)

ETS (180, 200, 225, 250)

ETS (180, 200, 225, 250)

15’

20’

30’

40’

50’

60’

70’

80’

17’3”

22’3”

32’3”

42’3”

52’3”

62’3”

72’3”

82’3”

ETU (40, 50, 60, 75)

ETU (50, 60, 75, 80, 90,
100, 110, 120, 130)

ETU (80, 90, 100, 110, 120,
125, 130, 140, 150, 160, 175)
ETU (125, 130, 140, 150,
160, 175, 180, 200, 225, 250)

ETU (180, 200, 225, 250)

ETU (180, 200, 225, 250)

ETU (180, 200, 225, 250)

MODEL

MODEL

ETS/U 40

ETS/U 50

ETS/U 60

ETS/U 75

ETS/U 80 & 90

ETS/U 100 & 110

10 feet

11 feet

12 feet

13 feet

13 feet

14 feet

9 feet

10 feet

11 feet

12 feet

12 feet

13 feet

ETS/U 120 & 125
ETS/U 130 & 140

ETS/U 150

ETS/U 160 & 175

ETS/U 180 & 200

ETS/U 225 & 250

14 feet

15 feet

15 feet

16 feet

18 feet

20 feet

13 feet

14 feet

14 feet

15 feet

17 feet

19 feet

HEIGHT AT

HORIZONTAL

HEIGHT AT

45° ANGLE

ETS/U (40, 50)

ETS/U (60, 75)

ETS/U (80, 90)

ETS/U 100

ETS/U (110, 120, 125, 130)

ETS/U (140, 150, 160, 175)

ETS/U (180, 200, 225, 250)

MINIMUM CLEARANCES TO COMBUSTIBLES

MODEL NO.

SIDE

CEILING

BELOW

END

(45°)

FRONT

(45°)

REAR

HORIZONTAL

27”

27”

52”

66”

66”

84”

86”

6”

6”

6”

6”

6”

6”

18”

40”

60”

84”

88”

101”

106”

132”**

30”

30”

30”

40”

40”

48”

48”

48”

48”

52”

66”

66”

84”

84”

12”

12”

12”

20”

20”

24”

24”

*When used indirect vented, clearances to ceiling from top of exhaust hood must be 12” on ETS/U (40-75), and 18” on
ETS/U (80-250). If optional corner or U-bend reflectors are not used, clearance must be 18”. **Clearance below the heater
is 132” for the first 20 ft. of the emitter tube and reduces to 72” 20 ft. downstream from the control box.
Note: Consult factory if reduced clearances are required.

This chart is intended as a guide only, as heaters may be mounted at various heights and angles. Since straight tube heaters are always hotter at the burner end than
at the exhaust end, always observe the minimum recommended mounting heights shown above. Use ETU series for spot heating. Please consult your local Space-
Ray Representative for a detailed analysis of your particular infrared heating requirements.

20’

30’

40’

50’

60’

70’

80’

12’9”

17’9”

22’9”

27’9”

32’9”

37’9”

42’9”

L

L

18”

18”

9”

13”

6”

15”

Control
Box

Draft
Inducer

18”

31”

6”

45° ANGLE

(MAXIMUM)

HEIGHT AT

HORIZONTAL

HEIGHT AT

45° ANGLE

1/2