These instructions apply to the field
installation of end switch kits on Greenheck
model WD Backdraft Dampers. These end
switch kits can be used in conjunction
with MP-100, MP-200, and MP-300 Series
actuators.

End switches are typically wired to a fan
and/or to a light serving as an open/not open
indicator. When the damper is powered open,
one of the damper blades makes contact with
the spring rod of the end switch which in turn
makes a connection allowing power to flow to
the fan and/or light. This set up would be used
when it is desirable to ensure that the damper
is fully open before the fan starts.

Instructions:

1. Position end switch such that the back side of damper blade trips

the spring rod.

2. Mount end switch bracket to damper frame or ductwork using

#10 x

1

2

in. self-drilling sheet metal screws

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Spring Rod

Spring Rod

2

3

3

4

1

2

3

3

4

1

End Switch Installation On

WD-100 Series Dampers

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Spring Rod

Spring Rod

2

3

3

4

1

2

3

3

4

1

End Switch Installation On

WD-200 & 300 Series Dampers

Part Number 452723

End Switch Kit

For use on WD series Dampers

Part # Qty.

Description

1

1

End switch mounting bracket

2

1

End switch
UL/CSA Rating L67
15 Amps: 125, 250, or 480 VAC
0.25 Amps: 250 VDC
0.50 Amps: 125 VDC

3

2

#6-32NC x 11/2 in. machine screws with
nuts (packaged in end switch housing)

4

2

#10 x 1/2 in. self-drilling sheet metal
screws

Field Installation Instructions

Copyright © 2008 Greenheck Fan Corporation

#452723 End Switch Rev 3 Aug 2008

Common

L1

Wiring Illustration

End

Switch

M

Green

Fan or

Light

N.C.

N.O.

L2

Damper

Actuator

Wiring Illustration

Note: Some actuators are multi-tap, use correct connections per
actuator wiring diagram.