P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE

APPLICATION EXAMPLE

3.

Select the

PQMII.D01

file from the list and click on Open.

4.

The software will display a list of the most commonly used parameters configured for
the PQMII.

Figure 9-9: Parameters configured for PQMII

5.

The Modbus User Map values are already present in the configuration file; as such, it is
not required to create the new parameters. However, it is necessary to save number of
registers to be read. Change the data length to 7 words as required.

6.

Similarly, load the configuration file for MM2 by clicking the Load Device button and
selecting the

MM2-MM3.DO1

file.

Figure 9-10: Parameters configured for the MM2

7.

The software will display a list of the most commonly used parameters configured for
the MM2. The Modbus User Map values are already present in the configuration file; as
such, it is not required to create the new parameters. However, it is necessary to save
number of registers to be read. Change the data length to 5 words as required.

8.

The Motor Start A command and Motor Stop command can be executed using
command function + operation code.

9.

Save this device configuration by clicking the Save Device button.

10. Click Next to proceed to step 4 of the configuration wizard.