Generac, Guardian, Series standby generator - 60 kw – Generac Guardian Series Standby Generators QT060 User Manual

Page 3: Operating data

Advertising
background image

OPERATING DATA

KW RATING (LP/NG)

60/60

ENGINE SIZE

2.4 Liter 4 cyl. inline

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/240V, 1-phase, 1.0 pf
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf
277/480V, 3-phase, 0.8 pf

60
60
60
60

250
208
180

90

300
250
200
100

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load*

For Btu content, multiply ft

3

/hr x 2520 (LP) or ft

3

/hr x 1000 (NG)

Natural Gas

(ft

3

/hr.)

123
267
483
672
862

Propane

(gal/hr.)

cu ft/hr

1.34

49.3

2.7

101

5.0

183

7.0

255

9.0

327

ENGINE COOLING

Air flow

(inlet air including alternator and combustion air)

ft

3

/min.

System coolant capacity

US gal.

Heat rejection to coolant

BTU/hr.

Max. operating air temp. on radiator

°C (°F)

Max. ambient temperature

°C (°F)

3,280

2.5

270,000

60 (150)
50 (140)

COMBUSTION AIR REQUIREMENTS

Flow at rated power 60 Hz

cfm

180

SOUND EMISSIONS IN DBA

Exercising at 7 meters
Normal operation at 7 meters

65
72

EXHAUST

Exhaust flow at rated output 60 Hz

cfm

Exhaust temp. at muffler outlet

°F

494

1,050

ENGINE PARAMETERS

Rated synchronous RPM

60 Hz

3600

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature Deration

3% for every 10 °C above - °C

1.65% for every 10 °F above - °F

Altitude Deration

1% for every 100 m above - m

3% for every 1000 ft. above - ft.

25
77

915

3000

* Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
ISO-3046-1. Design and specifications are subject to change without notice.
KW rating is based on LPG Fuel and may derate with natural gas.

Generac

®

Guardian

®

Series Standby Generator - 60 kW

®

Advertising