Section 2 — Post Installation Start-up and Adjustments

Generac Air-cooled 7 kW, 12 kW and 15 kW Generators

6. When frequency is correct at no load, check the

AC voltage reading. If voltage is incorrect, the volt-
age regulator may require adjustment.

Figure 2.3 — Single Cylinder Engine Governor

Adjustment

2.7.2

12 KW AND 15 KW UNITS

1. Loosen governor clamp bolt (See Figure 2.4).

Figure 2.4 — V-twin Engine Governor

Adjustment

2. Completely remove the idle spring.
3. With governor arm at wide open throttle position,

rotate governor shaft fully clockwise. Tighten
clamp bolt to 84 inch-pounds.

4. Start unit and apply full load. Use full load speed

adjust screw (Figure 2.5) to adjust frequency to
58 Hz.

5. Remove load, stop engine, loosen the idle adjust

screw and reconnect the idle spring.

6. Using a hand, push the governor arm to the

closed throttle position. Make sure the idle spring
does not stretch at all.

7. Restart the unit.
8. Slowly turn the idle adjust screw to adjust the no-

load idle frequency to 63-63.5 Hz.

9. The governor is now set.

Figure 2.5 — V-twin Full Load Speed Adjust

Screw

2.7.3

ADDITIONAL CORROSION
PROTECTION

Periodically spray all engine linkage parts and brack-
ets with corrosion inhibiting spray such as WD-40 or
a comparable product.

2.8

VOLTAGE REGULATOR
ADJUSTMENT

With the frequency between 62-63.5 Hertz, slowly
turn the slotted potentiometer (Figure 2.6) until line
voltage reads 244-252 volts.

NOTE:

Remove the access panel on top of the control
panel to adjust the voltage regulator.

Figure 2.6 – Voltage Adjustment Potentiometer

Full Load Speed Adjust Screw

Governor Clamp Bolt

Governor
Shaft

(Rotate
Clockwise)

Idle Spring

No Load Idle
Adjustment Screw

GOVERNOR

SHAFT

ADJUST

SCREW

GOVERNOR

CLAMP

BOLT