2 emergency circuit isolation method, 3 total circuit isolation method, 4 grounding the generator – Generac 004373-1 User Manual

Page 11: 5 generator ac neutral connections, 6 transfer switch start signal connections

Advertising
background image

Generac

®

Power Systems, Inc.

9

Figure 2.1 – Basic Standby Electric System

2.2 EMERGENCY CIRCUIT ISOLATION

METHOD

This prevents overloading the generator by keeping elec-

trical loads below the wattage/amperage capacity of the

generator. If the generator is powering only critical

loads, within its wattage/amperage capacity, during util-

ity power outages, consider using the emergency circuit

isolation method.
Critical electrical loads are grouped together and wired

into a separate “Emergency Distribution Panel.” Load

circuits powered by that panel are within the

wattage/amperage capacity of the generator set. When

this method is used, it is difficult to overload the gener-

ator. The transfer switch must meet the following

requirements:
• It must have an ampere rating equal to or greater

than the total amperage rating of the emergency dis-

tribution panel circuit.

• It must be installed between the building’s main distri-

bution panel and the emergency distribution panel.

2.3 TOTAL CIRCUIT ISOLATION METHOD

When a generator capable of powering all electrical

loads in the circuit is to be installed, use the “Total

Circuit Isolation Method.” It is possible for the genera-

tor to be overloaded when this isolation method is

employed. The following apply to the transfer switch in

this type of system.
• Ampere rating of the transfer switch must be equal to

or greater than the ampere rating of the normal

incoming utility service.

• The transfer switch must be installed between the

utility service entrance and the building distribution

panel.

2.4 GROUNDING THE GENERATOR

The National Electrical Code requires the frame and

external electrically conductive parts of this equipment

to be properly connected to an approved earth ground

and/or grounding rods. For that purpose, a GROUND

LUG (Figure 2.2) is provided on the generator mounting

base. Consult a qualified electrician for grounding

requirements in your area. Grounding procedures must

meet local regulations.

Do not connect the ground wire to any pipe that
carries a flammable or explosive substance – FIRE
or an EXPLOSION may result.

Proper grounding helps protect personnel against electri-

cal shock in the event of a ground fault condition in the

generator or in connected electrical devices. In addition,

grounding helps dissipate static electricity that often

builds up in ungrounded devices.

Figure 2.2 – Generator Grounding Lug (typical)

2.5 GENERATOR AC NEUTRAL

CONNECTIONS

Generac uses an UNGROUNDED AC neutral. Grounding
is recommended only at the main service entrance.

2.6 TRANSFER SWITCH START SIGNAL

CONNECTIONS

2.6.1 “GTS” Type Switch

Connect the two-wire start signal from the automatic
transfer switch to the automatic start connection, which is
located in the right hand corner inside the lower panel.
Match wires 178 and 183 in the transfer switch to 178
and 183 on the terminal strip in the control panel. The
conductors for the two-wire start circuit must be in their
own conduit.

2.6.2 Pre-Packaged Type Switch

Connect the six signal wires from the automatic trans-
fer switch to the engine generator control, which is
located on the upper right side and inside the lower
control panel. Match wires 23, 194, N1, N2, T1 and T2
in the transfer switch to the corresponding wires on the
terminal strip in the lower panel. The conductors for
these wires must be in seperate conduit from the main
AC output wires.

Section 2 — Installation

Guardian Liquid-cooled 40 kW Generator

Advertising
This manual is related to the following products: