Ductwork table, Plan ductwork, Ductwork table plan ductwork – GE JVB65 User Manual

Page 8: Installation instructions, Plan the ductwork, Continued)

Advertising
background image

INSTALLATION INSTRUCTIONS

(continued)

8

Plan the Ductwork

1. This downdraft blower system is designed
for use with 3

1

4

x 10

ductwork (can be transitioned

to 6

round). Three different discharge

directions are available with side--to-side
adjustment for accurate alignment of ductwork.
2. For best performance: Choose the ducting
option which allows the shortest length of
ductwork and a minimum number of elbows and
transitions. Check location of floor joists, wall
joists, wall studs, electrical wiring or plumbing
for possible interference.
NOTE: The unit is shipped with the 3

1

4

x 10

discharge facing DOWN. See the Changing
Blower Direction section, if necessary.

Steps to Determine Flexible Ducting’s
Equivalent Length

1. Measure the actual amount of offset
(Maximum 3

recommended). The effect upon

airflow is dependent upon the amount of offset.
2. Calculate the equivalent ducting allowances
using:

( ___ in. offset) x (14 Ft. per inch)
= ___ Ft. equivalent length.

3. Ensure that the total equivalent length of
ducting does not exceed the maximum
recommendation of 100 feet.

Right
discharge

Down discharge
(as shipped)

Left discharge

Duct Pieces

Equivalent Length*

Duct Pieces

Equivalent Length*

3

1

4

x 10

6

Round

to 6

Round

5 ft.

Straight

1 ft. (per foot length)

Transition

6

Round

to 3

1

4

x 10

3

1

4

x 10

1 ft. (per foot length)

Transition

20 ft.

Straight

90° Elbow

3

1

4

x 10

to 6

Round

6

15 ft.

Transition

12 ft.

90° Elbow

90° Elbow

6

Round

6

Wall Cap

21 ft.

45° Elbow

9 ft.

with Damper

3

1

4

x 10

3

1

4

x 10

Wall Cap

27 ft.

90° Elbow

16 ft.

with Damper

3

1

4

x 10

6

Round

45° Elbow

5 ft.

Roof Cap

20 ft.

3

1

4

x 10

6

Round

90° Flat Elbow

24 ft.

Roof Vent

24 ft.

6

Round

to 3

1

4

x 10

7 ft.

Transition

SHOULD NOT EXCEED 100 EQUIVALENT FT.
*Equivalent lengths of duct pieces are based on actual tests conducted by

GE Evaluation Engineering and reflect requirements for good venting
performance with a downdraft rated at 500 CFM.

29

1

/

2

Venting Island to Outside Wall

Wall

7

24

Power

Cord provided
(on-right-hand side)