Installation – Stovax 7129 User Manual

Page 8

Advertising
background image

8

INSTALLATION

2.7

The system vent should be a minimum diameter of 22mm and fitted with an air

separation device.

2.8

The Heat Sink (Slumber circuit) must be rated to suit the minimum heat output at slow

running, and have no manual or automatic closing valves fitted.

2.9

Thermostatic flow controls (90°C flow and 55°C return) should be fitted to the hot

water system. These would override the manual pump switch to maintain an

acceptable boiler temperature and ensure sufficient heat loss in an over-firing situation.

Fluid filled thermostats should be use of bi-metalic thermostats is not recommended.

2.10 The system should operate between 60°C and 80°C and not be allowed to drop in

temperature below 55°C. Large quantities of low temperature water passing through

the boiler could cause condensation to form in the firebox of the stove, and shorten the

life of the product.

2.11 A indirect 190 litre (40 gallon) or larger hot water storage cylinder, with a double feed,

complying to BS 1566 Part 1 type 10 should be fitted. This should be positioned

vertically as near as possible to the appliance and with sufficient height to allow gravity

flow. The water draw off pipes to the taps should be in a dead leg connection from the

vent pipe.

2.12 The water circuit must be fitted with suitable isolation and drain points to enable all

water to be removed for maintenance purposes.

2.13 If one flow and one return connection are to be used on the boiler use the connections

that are diagonally opposite each other on the back of the boiler.

Electrical Supply

2.14 Any electrical connections should comply with the requirements of the current Building

and Wiring regulations.

2.15 The connection to the mains supply should allow complete electrical isolation and only

serve the heating circuit pump.