Operating Manual LP 33 Series 50 & 60 kVA

Code

Message

Meaning

4602

Q1

OPEN

The auxiliary contact indicates that the output switch Q1 has
been opened.

4603

Q1

CLOSED

The auxiliary contact indicates that the output switch Q1 has
been closed.

4699

BATTERY TEST

IMPOSSIBLE

Not possible to start battery test (it is postponed) for:
• No mains rectifier or bypass;
• Battery not fully charged;
• Load is below 10% or above 80%.

4763

REMOTE CONTROL

ON

Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel.
1 = Only serial port on CI (TLC).
2 = Both.

4764

REMOTE CONTROL

OFF

Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel.
1 = Only serial port on CI (TLC).
2 = Both.