Auxiliary controls on your zoneline – GE 5500 User Manual

Page 6

Advertising
background image

6

Auxiliary controls on your Zoneline.

Remote Thermostat–Class 2

When this switch is enabled (UP), it allows the
unit to operate off of a Class 2 Remote Control
Wall Thermostat. The unit controls are disabled.

Load Shedding (CDC)

This feature is active only if the unit is in
CDC mode. When this switch is enabled (UP),
the indoor fan can be turned ON or OFF with
the unit controls.

Freeze Sentinel

When this switch is enabled (UP), it turns OFF
the freeze sentinel protection feature. With the
switch disabled (DOWN), the freeze sentinel is
activated which automatically provides heat
without user interface. This helps to prevent
plumbing damage by turning the heater and
indoor fan ON at 41° F and OFF at 46°F.

Constant ON Fan

When this switch is enabled (UP), it allows the
indoor fan to run continuously, at high speed,
even if the unit is in the STOP position.

Occupancy Sensor

When this switch is enabled (UP), it allows the
unit to utilize an infrared motion sensor and a
door switch for occupancy detection. This feature
allows an energy management system to be
installed and operated in conjunction with
the unit.

Customer Service

Troubleshooting T

ips

Care and Cleaning

Operating Instructions

Safety Instructions

CLASS 2 (Remote Thermostat)

LOAD SHEDDING (CDC)

FREEZE Sen (Freeze Sentinel)

CONST FAN (Constant
ON Fan)

OCCUPIED
(Occupancy Sensor)