Before you call for service, Normal operating sounds – GE 10 AZA User Manual

Page 26

Advertising
background image

Consumer Support

Troubleshooting T

ips

Installation Instructions

Care and Cleaning

Operating Instructions

Safety Instructions

26

Before You Call For Service…

Troubleshooting Tips
Save time and money! Review the chart on this page
first and you may not need to call for service.

Problem

Possible Causes

What To Do

Air conditioner

The air conditioner

Make sure the air conditioner plug is pushed completely

does not start

is unplugged.

into the outlet.

The fuse is blown/circuit

Check the house fuse/circuit breaker box and replace

breaker is tripped.

the fuse or reset the breaker.

Power failure.

If power failure occurs, turn the mode control to
OFF.

When power is restored, wait 3 minutes to restart

the air conditioner to prevent tripping of the

compressor overload.

Air conditioner does

Airflow is restricted.

Make sure there are no curtains, blinds or furniture

not cool as it should

blocking the front of the air conditioner.

The temp control may not

Turn the knob to a warmer or cooler setting. The coolest

be set high or low enough.

setting provides maximum cooling. The warmest setting

provides maximum heating on models with heat.

The air filter is dirty.

Clean the filter at least every 30 days. See the Care and
cleaning of the air conditioner

section.

The room may have been hot

When the air conditioner is first turned on you need to

or cold.

allow time for the room to cool down or warm up.

Cold air is escaping.

Check for open furnace floor registers and cold

air returns.

Set the air conditioner’s vent to the closed position.

Cooling coils have iced up.

See “Air conditioner freezing up” below.

Air conditioner

Ice blocks the air flow

Set the mode control at HIGH FAN or HIGH COOL

freezing up

and stops the air conditioner

with the temp at a warmer setting.

from cooling the room.

Normal Operating Sounds

You may hear a pinging noise caused
by water being picked up and thrown
against the condenser on rainy days or
when the humidity is high. This design
feature helps remove moisture and
improve efficiency.

You may hear the thermostat click
when the compressor cycles on and off.

Water will collect in the base pan
during high humidity or on rainy days.
The water may overflow and drip from
the outdoor side of the unit.

The fan may run even when the
compressor is not.

Advertising