Typical wiring diagrams—dpdt, Typical wiring diagrams—spdt, Setting the current time – GE 120VAC User Manual

Page 2: Programming on/off settings, Multiple weekday groups, Programming countdown operation, Figure 1

Advertising
background image

TIMERN

CN O

COM NC2 NO2 COM2

LOAD

L1

L2

TIMERN

CN O

COM

TO 200/240/277V LINE

TO 120V LINE

NC2 NO2 COM2

H

N

LOAD

TIMERN

CN O

COM

TO 24V LINE

NC2 NO2 COM2

H

N

LOAD

N
H

TO 120V LINE

TO LOAD

T

T

T

120V Timer, 120V Load and 24V Load

Wired as Single Throw

200/240/277V Timer, 200/240/277V Load, Double Break

Wired as Single Throw

120V Timer, 200/240/277V Load Double Break

Wired as Single Throw

Typical Wiring Diagrams—DPDT

TO POWER SUPPLY

TO POWER SUPPLY 1

TO POWER SUPPLY 2

Timer and Load, Same Voltage

Wired as Single Throw

TO LOAD

TO 120V LINE

H

N

HIGH

LOW

COM

T

LOAD

T

NC

TIMERN

OC OM

TIMERN

CN OC OM

T

TIMERN

CN OC OM

120V Two Speed Fan

Wired as Double Throw

Timer and Load, Different Voltage

Wired as Single Throw

Typical Wiring Diagrams—SPDT

Field Wiring

Timer Internab Wiring

FIGURE 1

Override

(Manual ON/OFF Switched)

Timer

(9 Programs Setting)

Clock

(Current Time Setting)

LCD

(Function Figures)

R

(Reset)

H-

(Hours Setting)

M-

(Minutes Setting)

Day

(Days Setting)

OPERATING INSTRUCTIONS

BASIC SETTINGS:

Initial Set Up:

1. Push the “R” button before programming to clear out any settings. Once

the “R” button is pressed the screen will begin to flash. A paperclip may
be needed for this step.
(If the “R” button appears to stick down, use a toothpick to maneuver
it until it pops back up. The screen will flash if the button is popped up
successfully.)

2. Press the “Clock” button and the screen will stop flashing and be ready

for programming.

Setting the Current Time:

1. Press and Hold the “Clock” button during the entire setting.
2. Press the “H+” button to set the hours.
3. Press the “M+” button to set the minutes.
4. Press the “Day” button to set the day of the week.
5. Release the “Clock” button.

Programming ON/OFF Settings:

1. Press the “Timer” button once and the TIMER 1 ON - - : - - appears.
2. Press the “H+” and “M+” button to set the hours and minutes to the

desired time.

3. Press the “Day” button to select the day(s) the setting will be active. Refer

to the Multiple Weekday Group below to see the available settings.

4. Press the “Timer” button to store the setting and proceed to the next

setting TIMER 1 OFF - - : - -.

5. Repeat for all remaining setting options (9 Total ON/OFF settings). Once

completed press the “Clock” button to return to the main display.

Multiple Weekday Groups:

Apart from individual week days, pressing the “Day” button also selects
multiple day combinations such as:
- Monday thru Friday

- Tuesday & Thursday & Saturday

- Saturday & Sunday

- Monday thru Wednesday

- Monday thru Saturday

- Thursday thru Saturday

- Monday & Wednesday & Friday

- Monday thru Sunday

After setting a single day or a multi-day-combination the programmed timer
settings will be carried out on each of the week-days at the same time.

Programming Countdown Operation:

1. Press the “Timer” button to scroll through the 9 events settings to get to

the ON C setting.

2. Press the “Override” button to select whether the timer will turn ON or OFF

during teh countdown period.

3. Press the “H+” and “M+” buttons to set the hours and minutes of the

countdown.

4. Press the “Clock” button to store the setting and return to the current time

display. See the diagram below for more information.

PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE

INSULATION CLEARS

PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14

12

10

8

15

20

30

40

60

60

60

105

1/2

1

2

-

2

2 1/2

3

5

N/A

N/A

Advertising