Dvb4136 direct vent gas fireplace, Final finishing, Gas specifications – Majestic Appliances DVB4136 User Manual

Page 8: Gas inlet and manifold pressures, High elevations, Gas line installation

Advertising
background image

8

DVB4136 Direct Vent Gas Fireplace

20012322

J

F

G

H

I

Mantel

Leg

CFM164a

Mantel Leg Chart

06/22/01 sta

CFM170

DV Builder Front

View

O

N

M

L

K

Black

Surround

Face

CFM164a

Side of

Combustion Chamber

CFM170

Mantel

Mantel Leg from Side

Ref.

Leg Depth

Ref.

of Comb. Opening

F

10” (254 mm)

K

11¹⁄₂” (292 mm)

G

8” (203 mm)

L

9¹⁄₂” (241 mm)

H

6” (152 mm)

M

7¹⁄₂” (191 mm)

I

4” (101 mm)

N

5¹⁄₂” (140 mm)

J

2” (51 mm)

O

3¹⁄₂” (89 mm)

Fig. 4b Combustible mantel leg minimum installation.

������
���������������
����

A

B

Flange

Drywall

Position

Depth

A

1/2” / 13 mm

B

5/8” / 16 mm

Flange Location for

Desired Drywall Depth

FP1539

Fig. 5 Drywall flange location.

Final Finishing

Noncombustible materials such as brick or tile can be
extended over the edges of the face of the fireplace.
Do not cover the window frame assembly, any vent,
louvre assembly top or louvre assembly bottom.
If
a Trim Kit is to be installed, brick and tile will have to be
installed flush with the side of this appliance.

Gas Specifications

Max.

Min.

Gas

Input

Input

Model

Fuel

Control

BTU/h BTU/h

DVB4136RN Natural Gas Millivolt Hi/Lo

30,000 18,500

DVB4136RP

Propane

Millivolt Hi/Lo

30,000 17,000

DVB4136IN

Natural Gas 24 Volt Hi/Lo

30,000 21,800

DVB4136IP

Propane

24 Volt Hi/Lo

30,000 21,300

DVB4136RFN Natural Gas Comfort Control 30,000 21,000
DVB4136RFP

Propane

Comfort Control 30,000 23,500

Gas Inlet and Manifold Pressures

Natural

LP (Propane)

Minimum Inlet Pressure

5.5” w.c.

11.0” w.c.

Maximum Inlet Pressure

14.0” w.c.

14.0” w.c.

Manifold Pressure

3.5” w.c.

10.0” w.c.

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).

Gas Line Installation

When purging gas line the front glass
must be removed.

The gas pipeline can be brought in through the right
side of the appliance. Knockouts are provided at conve-
nient locations to allow for the gas pipe installation and
testing of any gas connection.
The gas line connection can be made with properly
tinned 3/8” copper tubing, 1/2” rigid pipe or an approved
flex connector. Since some municipalities have addi-
tional local codes, it is always best to consult your local
authority and the CSA-B149.1 installation codes.
For USA installations consult the current National Fuel
Gas Code, ANSI Z223.1/NFPA 54.

3/4” (19 mm) Scribe
Moulding for use with
CFM Cabinets