SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. 120 Volt And 240 Volt Duplex Receptacles

190 376

Y Be sure equipment connected to the

240 V receptacles is GFCI-pro-

tected.

.

Generator power is not affected by
position of Welder Selector switch.

.

4 kVA/kW generator power output is
shared by all receptacles.

1

240 V 20 A AC Receptacle RC1

2

120 V 20 A AC GFCI Receptacle

GFCI 1

3

240 V 20 A AC Receptacle RC2

4

120 V 20 A AC GFCI Receptacle

GFCI 2

Receptacles supply 60 Hz single-phase

power at weld/power speed.
If a ground fault is detected, the GFCI re-

ceptacle(s) circuit opens to disconnect the

faulty equipment and the GFCI Reset but-

ton pops out. Check for damaged tools,

cords, plugs, etc. connected to the recep-

tacle. Press button to reset receptacle and

resume operation.

.

At least once a month, run engine at
weld/power speed and press Test but-
ton to verify GFCI is working properly.

5

Circuit Breakers CB1 And CB2

6

Circuit Breakers CB3 And CB4

CB1 and CB2 protect RC1 and GFCI 1 from

overload. If CB1 or CB2 opens, RC1 does

not work. 120 volts may still be present at

RC1. If CB2 opens, GFCI 1 does not work.

Press button to reset breaker.
CB3 and CB4 protect RC2 and GFCI 2 from

overload. If CB3 or CB4 opens, RC2 does

not work. 120 volts may still be present at

RC2. If CB4 opens, GFCI 2 does not work.

Press button to reset breaker.

.

If a circuit breaker continues to open,
contact Factory Authorized Service
Agent.

Maximum output from each 120 volt GFCI

receptacle is 2.4 kVA/kW. Maximum output

from each 240 volt duplex receptacle half is

4.0 kVA/kW.
Total combined output from all receptacles

is 4 kVA/kW.
EXAMPLE: If 12 A is drawn from RC1, only

9 A is available at GFCI 1:
(240 V x 12 A) + (120 V x 9 A) = 4.0 kVA/kW

.

Generator power is not affected by
weld output.

1

5

2

3

6

4

SECTION 8 − MAINTENANCE & TROUBLESHOOTING

8-1. Routine Maintenance

Recycle

engine

fluids.

Y Stop engine before maintaining.

.

See Engine Manual and Maintenance Label for im-
portant start-up, service, and storage information.
Service engine more often if used in severe condi-
tions.

*

To be done by Factory Authorized Service Agent.

Every 8 h

Check Fluid

Levels. See

Section 5-5.

Wipe

Up

Spills.

Drain Water

From Fuel

System. See

Section 8-4.

OIL

Full

FUEL

WATER

Every 50 h

Clean Air Filter.

See Section 8-3.

Clean And

Tighten

Weld

Terminals.