Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)

1598003200

6


13. PARAMETER MAP

LABEL

DESCRIPTION

VALUE

LEVEL

RANGE

ot

Thermostat probe
calibration

0 Pr2

[-12,0°C <> 12,0°C] [-

21°F <> 21°F]

CF

T° measurement unit

F

Pr2

°C(0) - °F(1)

rES

Resolution (only °C)

in

Pr2

dE(0) - in(1)

UT

Display update

60

Pr2

0 <> 255 (s)

OnF

Off function enabling

y

Pr2

n(0) - Y(1)

ALU

High Tempalarm setting

50 Pr1

°C[ ALL <> 150,0°] °F[

ALL <> 302°]

ALL

Low Temp alarm setting

30 Pr1

°C[ -50.0° <> ALU] °F[-

58 <> ALU]

AFH

Temp alarm differential

2 Pr2

[0,1°C <>25,5°C] [1°F

<> 45°F]

ALd

Temp alarm delay

30

Pr1

0 <> 255 (min.)

dAo

Delay of Temp alarm at
start-up

1.3 Pr2

0 <> 24H0(144)

EdA

Alarm delay at the end
of defrost

30 Pr2

0 <> 255 (min.)

dot

Delay of Temp alarm
after closing the door

15 Pr2

0 <> 255 (min.)

LHt

Light timer

15

Pr1

0 <> 255 (min.)

doA

Open door alarm delay

15

Pr1

0 <> 255 (min.)

OA1

First relay configuration

ALr

Pr2

ALr(0) - LHt(1) - OnF(2)

oA2

Second relay
configuration

LHt Pr2

ALr(0) - LHt(1) - OnF(2)

AOP

Alarm relay polarity

oP

Pr2

OP - CL

i1P

Digital input 1 polarity

oP

Pr2

OP(0) - CL(1)

i1L

Door switch to turn light
ON

y Pr2

n(0) - Y(1)

i1F

Digital input 1 operating
mode

dor Pr2

EAL(0) - dor(1) - dEr(2)

- LHt(3)

i2P

Digital input 2 polarity

cL

Pr2

OP(0) - CL(1)

i2F

Digital input 2 operating
mode

PA

n

Pr2

EAL(0) - Pan(1) -

dFr(2) - LHt(3)

did

Time interval/delay for
digital input alarm

0 Pr2

0 <> 255 (min.)

tbA

Alarm relay disabling

n

Pr2

n(0) - Y(1)

PbC

Kind of probe

ntc

Pr2

PtC(0) - ntC(1)

dP1

Real T° Probe 1

Pr2

(probe value)

rEL

FW release

Pr2

read only

Ptb

Parameter map

Pr2

read only