4-7. Connecting 3-Phase Input Power

2/04 - Ref. 802 136-A / 801 192

!

Installation must meet all National

and Local Codes − have only quali-

fied persons make this installation.

!

Disconnect and lockout/tagout in-

put power before connecting input

conductors from unit.

!

Always connect green or green/

yellow conductor to supply

grounding terminal first, and never

to a line terminal.

.

The Auto-Link circuitry in this unit au-

tomatically links the power source to

the primary voltage being applied. A

230/460 unit can be connected to ei-

ther 230 or 460 VAC input power. A

460/575 model can be connected to

either 460 or 575 VAC input power.

For Three-Phase Operation
1

Input Power Cord.

2

Disconnect Device (switch shown in

the OFF position)

3

Green Or Green/Yellow Grounding

Conductor

4

Disconnect Device Grounding

Terminal

5

Input Conductors (L1, L2 And L3)

6

Disconnect Device Line Terminals

Connect green or green/yellow grounding

conductor to disconnect device grounding

terminal first.
Connect input conductors L1, L2, and L3

to disconnect device line terminals.
7

Overcurrent Protection

Select type and size of overcurrent protec-

tion using Section 4-5 (fused disconnect

switch shown).
Close and secure door on disconnect

device. Remove lockout/tagout device,

and place switch in the On position.

= GND/PE Earth Ground

L1

2

1

L2
L3

3

3

4

5

6

7

Tools Needed: