Murphy Autostart 705 AS705S User Manual

Murphy Hardware

Advertising
background image

AUTOSTART 705 (AS705S series)

PROGRAMMABLE GENERATOR CONTROLLER

The Autostart 705 provides the control features for the
automatic or manual starting, load transfer and shutdown of
a standby diesel generator or pump. The AS705 is a micro-
processor based controller, giving full programmability of
timers, trip levels and control options, with front facia LEDs
for the indication of generator status and faults.

Key features

Automatic or manual operation, selected by rotary switch

(key-switch available as an option).

17 LED status and fault indicators, including 5 LEDs

for custom programming and labelling

RS232 communications link for engine monitoring,

control and Autostart programming from local PC

Comprehensive fault protection and alarm system:–

low oil pressure, high engine temperature, overspeed,
underspeed, charge fail, emergency stop, start fail, high
and low battery voltage, 3 programmable fault inputs.

6 programmable outputs, allowing remote signalling

and control of over 30 different functions.

Pin compatibility with Autostart 710 and Keystart 9700

ranges, allowing standardisation of panel wiring.

96 x 96mm DIN standard, front panel mounted case

Operation

Autostart’s operating mode is selected by use of its
3 position front facia switch:–

Off/reset. Disables the engine and resets a
latched fault condition.

Automatic start-up, load transfer and return to
standby in response to a mains fail or remote
start condition, with full fault protection.

Manual start and stop of the generator, either
immediately on selecting manual mode or by
use of remote push button switches.

Green and amber LEDs around the switch indicate the
selection of Auto and Manual modes. On keyswitch
versions, the key is common to all units and may be
removed in the Off and Auto positions only.

Control Outputs

The following are provided:-

Single pole, switched +ve relay outputs for the control

of engine fuel and starter motor circuits.

Switched +ve outputs for signalling auto and manual

modes, plus a –ve DC output for Off/reset.

6 function programmable outputs (see overleaf).

Fault Protection and Alarm System

In Auto or Manual modes, Autostart will shut down and latch
out the generator on detection of low oil pressure, high
engine temperature, overspeed, start fail or emergency
stop faults. The Autostart may also be set up to shut down
the generator on low generator frequency or speed.

3 additional inputs may be used with remote fault switches
(giving a ‘shutdown’ or ‘warning’ response), or as control
inputs with remote contacts or panel switches (see overleaf).

Non-latching, 'warning only' alarms are fitted for high and
low battery volts, charge fail and mag. pickup fail conditions.

The Generator Controls Division of

R

M011101

Issue 6, revised 06/99

Catalogue section 75

(MS5258)

Product Specification

Power supply:

Operating voltage: steady state range

crank brown-out

5 – 40 V DC continuous

to 0V for <= 100 mSec

Current consumption

typically 150 mA

Inputs:

DC inputs (inputs 1 - 5, remote start)

positive input voltage range

80% to 100% of battery +ve

negative input voltage range

–1V to +2V w.r.t. battery –ve

Generator AC input:-

operating voltage range

90 – 300 V AC rms

frequency measurement range

0 – 99 Hz.

Magnetic pickup:-

operating voltage range

7 – 80 V AC rms

frequency measurement range

0 to 10 kHz

Outputs:

(all ratings for resistive load)

Start and fuel relays

+ ve DC (switched SPNO contact)

rated 16A max. @ 24V DC

Programmable outputs 1 – 3

– ve DC (open collector transistor)

rated 250mA max. @ 33 VDC

Programmable output 4

– ve DC (switched SPNO contact)

rated 5A max. @ 24V DC

Programmable output 5

(default setting: Common Alarm)

+ ve DC (switched SPNO contact)

rated 5A max. @ 24V DC

Programmable output 6

(default setting: Gen. contactor)

volt free SPNO contacts

rated 5A max. @ 240V AC

Auto & Manual outputs

+ ve DC, 250mA max.

Off/reset output

– ve DC, 250mA max.

Physical:

Overall dimensions (W x H x D)

96 x 96 x 162 mm

Panel cut-out size

DIN standard 92 x 92 mm

Weight

approx. 650 g

Operating ambient temperature

–10 to +55

o

C

Case sealing

IP22