Ex rt cla module box contents – MGE UPS Systems EX RT CLA User Manual

Page 2

Advertising
background image

CLA Module (Long backup time charger)

(Part number 86004)

Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA module.

IMPORTANT

The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.

Battery backup time chart.

Battery Backup Time

Recommended Batteries

EX 5 RT

EX 7 RT

EX 11 RT

2 hours

50 Ah

65 Ah

100 Ah

4 hours

100 Ah

130 Ah

200 Ah

8 hours

200 Ah

200 Ah

400 Ah

Total battery voltage : 240 V DC (20 x 12V DC).

The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization sect

STEP 1 EX RT CLA Module Unpacking and Parts Check

EX RT CLA Module

EX RT CLA Module Installation

2

86-86000-04 AO

EX RT CLA Module
Installation and
User Manual

Power Cable

EX RT CLA Module Box Contents

Tower Stand Expanders

Battery Detection Cable

Stabilizer Bracket

(4 screws included)